Chapter 3Hardware Installation

3.1:

Mounting

the

Nexus

1250/1252

Meter

QThe Nexus 1250/1252 Meter is designed to mount against any firm, flat surface. Use a #10 screw in
each of the four slots on the flange to ensure that the unit is installed securely. For safety reasons,
mount the Meter in an enclosed and protected environment, such as in a switchgear cabinet. Install
a switch or circuit breakernearby; label it clearly as the meter ’s disconnecting mechanism.
NOTE: The Nexus Meter with Internal Modem Option mounts the same way.
QMaintain the following conditions:
Operating Temperature: -40°C to +70°C / -40°F to +158°F
Storage Temperature: -45°C to +85°C / -49°F to +185°F
Relative Humidity: 5 to 95% non-condensing
Electro Industries/GaugeTech
Doc # E107706 V1.253-1
Figure 3.1: Nexus Meter Mounting Diagram, Top View
4 x 0.221” (5.61mm) Thru Slot
(For #10 Screw)
2 x 3.25” (8.25cm) 2x4.0” (10.16cm)
10.5” (26.67cm)
7.25”
(18.41cm)
6.74”
(17.11cm)