Full-Load Loss Watts (kW) = 1-Phase Kw Load Loss = ______________

Full-Load Loss VA (kVA)

= (%Impedance) * (1-Phase kVA Self-Cooled Rating) / 100

 

= (______________) * (________________) / 100

 

= _______________ kVA

Full-Load Loss VAR (kVAR)

= SQRT((Full-Load Loss kVA)2 - (Full-Load Loss kW)2)

 

= SQRT((_________________)2 - (________________)2)

 

= SQRT((__________________) - (_________________))

 

= SQRT (_________________)

 

= _________________

Normalize Losses to Meter Base

Quantity

Value at Trf

M/T

M/T Factor

Exp

M/T Factor w/

Value at

Base

Factor

Value

Exp

Meter Base

 

 

 

 

 

 

 

 

 

No-Load Loss kW

 

V

 

2

 

 

No-Load Loss kVAR

 

V

 

4

 

 

Load Loss kW

 

I

 

2

 

 

Load Loss kVAR

 

I

 

2

 

 

Enter Value at Transformer Base for each quantity from calculations above. Enter Meter/Trf Factor value from Base Conversion Factor calculations above. Calculate M/T Factor with Exponent by raising the M/T Factor to the power indicated in the “Exp” (or Exponent) column.

Calculate the “Value at Meter Base” by multiplying the (M/T Factor w/ Exp) times the (Value at Trf Base).

Loss Watts Percentage Values

Meter Base kVA

= 600

* (PT Multiplier) * (CT Multiplier) / 1000

 

= 600

* (____________) * (___________) / 1000

 

= ________________