7.2.1.1: Three Element Loss Compensation Worksheet

Company

Date

Trf Manf

Calculation by

Station Name

Trf Bank No.

Trf Serial No.

Transformer Data (from Transformer Manufacturer’s Test Sheet)

Winding

 

Voltage

 

 

MVA

Connection

 

 

 

 

 

 

 

 

 

HV - High

 

 

 

 

 

 

- Y

 

 

 

 

 

 

 

 

 

Xv - Low

 

 

 

 

 

 

- Y

 

 

 

 

 

 

 

 

 

YV - Tertiary

 

 

 

 

 

 

- Y

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

 

 

Watts Loss

 

 

 

 

 

 

 

 

 

 

 

 

3-Phase

 

 

1-Phase

 

1-Phase kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No-Load Loss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load Loss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing

3-Phase values by three. Convert 1-Phase Loss Watts to 1-Phase kW by dividing 1-Phase Loss Watts by 1000.

Value

3-Phase MVA

1-Phase MVA

1-Phase kVA

 

 

 

 

Self-Cooled Rating

 

 

 

 

 

 

 

Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing 3-Phase values by three. Convert 1-Phase Self-Cooled MVA to 1-Phase kVA by multiplying by 1000.

% Exciting Current

% Impedance

Value

Phase-to-Phase

Phase-to-Neutral

 

 

 

Test Voltage (volts)

 

 

 

 

 

Full Load Current (Amps)

 

 

 

 

 

Test Voltage is generally Phase-to-Phase for three-phase transformers. Calculate Phase-to-Neutral Voltage by dividing Phase-to-Phase Voltage by √3. Calculate Full Load Current by dividing the (1-Phase kW Self-Cooled Rating) by the (Phase-to-Neutral Voltage) and multiplying by 1000.