2.8: Nexus External I/O Modules (Optional)
The following multiple analog or digital I/O modules mount externally to the Nexus 1250/1252 Monitor. The Nexus 1250/1252 Monitor supports up to four I/O modules using internal power. Use the additional power supply, EIG PSIO, to extend I/O capability. See section 3.4 for mounting diagrams. See Chapter 9 for details on installation and usage of the Nexus External I/O Modules.
Analog Transducer Signal Outputs (Up to two modules can be used with the Nexus 1250/1252.)
•1mAON4: 4 Analog Outputs, self powered, scalable, bidirectional.
•1mAON8: 8 Analog Outputs, self powered, scalable, bidirectional.
•20mAON4: 4 Analog Outputs, self powered, scalable.
•20mAON8: 8 Analog Outputs, self powered, scalable.
Analog Transducer Inputs (Multiple modules can be used.)
•8AI1: 8 Analog Inputs
•8AI2: 8 Analog Inputs
•8AI3: 8 Analog Inputs
•8AI4: 8 Analog Inputs
Digital Dry Contact Relay Outputs (Multiple modules can be used.)
•4RO1: 4 Relay Outputs 10 Amps, 125V AC, 30V DC, Form C.
Digital Solid State Pulse Outputs (Multiple modules can be used.)
•4PO1: 4 Solid State Pulse Outputs, Form A KYZ pulses.
Digital Inputs (Multiple modules can be used.)
•8DI1: 8 Digital status inputs Wet/Dry Auto Detect, up to 300V AC/DC.
Other I/O Accessories
•PSIO: Additional power supply for up to six I/O modules. This unit is necessary if you are connecting more than four I/O modules to a Nexus 1250/1252 Monitor.
•MBIO: Bracket for
e Electro Industries/GaugeTech Doc # E107706 V1.25 |