9.9: Digital Status Input Module

Digital Status Input Module Specifications

Model Number

8DI1

 

 

Communication

RS-485, Modbus RTU

 

Programmable Baud Rates: 4800, 9600, 19200, 57600

 

 

 

Power Requirement

15–20Vdcat 50–200 mA;

Nexus 1250/1252 Unit

 

supports up to 4 Modules

 

 

Operating Temperature

(-20 to 79)°C / (-4 to +158)°F

 

 

Voltage Rating

Up to 300Vdc

Detection

Wet/Dry, Auto Detect

 

 

Memory

256 byte I2C EEPROM for storage of Programmable

Settings and Nonvolatile Memory

 

 

 

 

Modbus Address: 164

Factory Settings

 

Baud Rate: 57600

 

 

 

Transmit Delay Time: 0

 

 

Default Settings

Modbus Address: 247

 

Baud Rate: 57600

(Reset Button)

 

 

Transmit Delay Time: 20 csec

 

 

9.9.1: Overview

The Digital Status Input Module is used for either additional status detect or for accumulating pulses from external equipment, such as power meters, water meters, etc.

Nexus 1250/1252 Unit supplies power for up to 4 connected Digital Status Input modules. See section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you must use an additonal power source, such as the EIG PSIO.

9.9.2: Communication

Maximum registers per request, read or write, is 4 registers.orm

The device will operate with the following Default Mode Parameters. See section 9.4.1 for details.

Address

247 (F7H)

Baud Rate

57600 Baud

Transmit Delay Time

20 csec

Electro Industries/GaugeTech Doc # E107706 V1.25

9-15

Page 127
Image 127