5.12: Steps to Determine Power Needed

Available power for All Ports of the Nexus 1250/1252 is 12 VA.

Refer to the table below to determine the VA Ratings for I/O modules and displays.

Add together the VA Ratings for I/Os and Displays in use.

Compare Available Power to Power Needed to determine if you must use an additional power source. EIG recommends the PSIO 12V power source. See section 9.2.1.

5.13: I/O Modules’ Factory Settings and VA Ratings

All I/Os are shipped pre-programmed with a baud rate of 57600 and addresses. The table below details the factory-set address for each module and the VA Ratings for I/O modules and Nexus displays. Refer to the previous section (section 5.12) for the steps to determine if you must use an additional power source. For programming, refer to Chapter 8 of the Communicator EXT User Manual.

I/O MODULES’ FACTORY SETTINGS AND VA RATINGS

 

MODEL NUMBER

MODULE

ADDRESS

VA RATING

1mAON4

0-1mA, 4 Analog Outputs

128

2.7 VA

1mAON8

0-1mA, 8 Analog Outputs

128

3.2 VA

20mAON4

4-20mA, 4 Analog Outputs

132

5.0 VA

20mAON8

4-20mA, 8 Analog Outputs

132

8.5 VA

8A11

0-1mA, 8 Analog Outputs

136

2.3 VA

8A12

0-20mA, 8 Analog Outputs

140

2.3 VA

8A13

0-5V DC, 8 Analog Outputs

144

2.3 VA

8A14

0-10V DC, 8 Analog Outputs

148

2.3 VA

4RO1

4 Latching Relay Outputs

156

2.7 VA

4PO1

4 KYZ Pulse Outputs

160

2.7 VA

8D11

8 Status Inputs (Wet/Dry)

164

1.0 VA

 

NEXUS DISPLAYS’ VA RATINGS

 

P40N, P41N or P43N

Nexus LED Display

 

8 VA

P60N

Nexus Touch Screen Display

 

5 VA

Electro Industries/GaugeTech Doc # E107706 V1.25

5-15

Page 73