Measurement Procedure

1.Original Signal with amplitude variations.

2.Square demodulator.

3.Weighted filter.

4.Low pass filter 1st order.

5.Statistical computing.

Data available

Pst, Pst Max, Pst Min values for long term recording Plt, Plt Max, Plt Min values for long term recording

 

 

 

 

Simulation Of Eye Brain Response

 

 

 

Block 1

 

 

Block 2

 

Block 3

Block 4

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

Detector

 

 

 

 

High Pass

 

 

 

 

 

and Gain

 

 

 

 

Filter

 

 

 

 

 

Control

 

 

Square

 

(DC

 

 

 

1st

 

 

 

 

Removal)

Weighting

 

Squaring

Order

 

 

 

Law

 

 

Sliding

 

 

 

 

 

Filter

Multiplier

 

 

 

Demodulator

 

Low

Mean

 

 

 

 

 

 

 

Input

 

 

 

 

Pass Filter

 

 

 

Filter

 

 

 

 

(Carrier

 

 

 

 

 

Voltage

 

 

 

 

Removal

 

 

 

 

 

Adaptor

 

Block 5

 

A/D

 

 

Minimum

 

Converter

Output

Sampling

64 level

Interface

Rate

Classifier

 

>50Hz

 

 

 

 

 

Programming of short and long observation periods

Output Recording

Output and Data Display

Instantaneous Flicker in

Pst Max/Min Pst

Perceptibility Units

Plt Max/Min Plt

(Pinst)

 

Figure 12.1: Simulation of Eye Brain Response

12.3: Setup

Initially the user must set up several parameters to properly configure Flicker. Using Communicator EXT, from the Icon Menu select Edit Device Profile. From the Device Profile, select Flicker Settings. The following screen will appear:

Electro Industries/GaugeTech Doc # E107706 V1.25

12-3

Page 137
Image 137