Gateway 312785C important safety instructions Alarm Processing Flow Chart

Models: 312785C

1 82
Download 82 pages 10.8 Kb
Page 26
Image 26

Modbus and I/O Data

Alarm Processing

See FIG. 29, Table 1, Table 2, and Table 3.

NO

Determine the exact alarm from Table 3 on page 29 and solve what caused the alarm, as required.

Reset the alarm.

Reset_Alarm = 1.

Alarm Processing

An Alarm Condition

has been found

previously.

Alarm_General = 1.

Check if Potlife

Alarm: is Alarm_

Potlife bit = 1?

YES

Two options:

Purge or Color Change to remove mixed material in the line.

Place in Mix mode and spray the Potlife Volume set in the ProMix 2KS.

NOTE: The Reset key only silences the alarm. To clear the alarm you must use one of these two options.

NO

YES

 

Is Mix Ready

 

bit = 1?

FIG. 29. Alarm Processing Flow Chart

Go to next process,

as desired.

26

312785C

Page 26
Image 26
Gateway 312785C important safety instructions Alarm Processing Flow Chart