Troubleshooting

Serial Communication Troubleshooting

This section is used to troubleshoot the communication between two devices linked via serial ports, i.e. RS232 or RS485.

TIP: For communication troubleshooting, it is strongly advised to create a new Graco Gateway database including only one data tag mapped to a known register in the target device.

PROBLEM

CAUSE

SOLUTION

 

 

 

 

 

 

Values show ----

Port settings do not match.

Check that the port settings of the

 

 

Graco Gateway device match the tar-

 

 

get device (i.e. Baud, Parity, etc.).

 

 

 

 

Incorrect target device address.

Check that the target device address

 

 

in Graco Gateway (in communica-

 

 

tions on the PLC symbol) matches

 

 

the target device address setup.

 

 

 

 

Incorrect cable.

Check the cable part number or

 

 

cabling to match your protocol.

 

 

 

 

Incorrect communication port.

Check if the cable is connected to the

 

 

correct communication port.

 

 

If the above is correct, check that the

 

 

protocol settings are on the correct

 

 

communication port in Graco Gate-

 

 

way.

 

 

 

 

Communication port connector pins

Although unlikely, check the commu-

 

bent inward.

nication port connector pins on the

 

 

Graco Gateway in case some are

 

 

bent inward resulting in a bad contact

 

 

with the cable.

 

 

 

 

Incorrect tag mapping.

Check that the tag is mapped to an

 

 

existing register in the target device.

 

 

 

Values blink between the data and

Incorrect tag mapping on one of the

Delete tags one after another and

----

tags on the display.

download in-between. When the val-

 

 

ues on the screen stop blinking, the

 

 

last deleted tag was mapped incor-

 

 

rectly or accessed an unknown regis-

 

 

ter in the target device.

 

 

 

 

Communications times-out.

Increase the Slave Response or

 

 

Device Timeout on the communica-

 

 

tion port or target device in Graco

 

 

Gateway.

 

 

 

36

312785C