Appendix C: Graco Gateway to ControlLogix via Ethernet IP

The following settings mirror the I/O settings of the ControlLogix configuration detailed earlier.

a.Input Connection Point. Create a Gateway block configuration (see Table 7).

Table 7: Input Connection Points

Connection Point

2

 

 

Data Offset

0000

 

 

Data Type

Long as Long

 

 

Block Size

2

 

 

Direction

Graco Gateway to Device

 

 

b.Output Connection Point. Create a Gateway block configuration (see Table 8).

Table 8: Output Connection Points

Connection Point

3

 

 

Data Offset

0000

 

 

Data Type

Long as Long

 

 

Block Size

2

 

 

Direction

Device to Graco Gateway

 

 

4.Data Mapping. the connection points are now con- figured so that:

Gateway_HMI:O >> PLC1:Block1 Gateway_HMI:I << PLC1:Block2

5.Testing. Using the RSLogix5000 program, you can modify tags Gateway_HMI:O and verify they are written into Var1 and Var2, and verify changes made in the Gateway to tags Var3 and Var4 are updated in Gateway_HMI:I. Ensure the device is in the Run mode, otherwise the data transfer will be ignored by the Gateway.