Troubleshooting

 

 

 

PROBLEM

CAUSE

SOLUTION

 

 

 

 

 

 

Unit shows “Version Mismatch”.

The database currently in the device

Download the database from Graco

 

does not match Graco Gateway’s

Gateway again.

 

firmware version. (Message occurs

 

 

after a download with a new version

 

 

of C2 interrupted before the database

 

 

was downloaded.)

 

 

 

 

Unit shows “Invalid Database”.

The database in the device is cor-

Download a database from Graco

 

rupted or there are no databases in

Gateway.

 

the device.

 

 

 

 

Values show ----

No communication with target device.

See Serial Communication Trou-

 

 

bleshooting (page 36) or Ethernet

 

 

Communication Troubleshooting

 

 

(page 37).

 

 

 

Value does not update.

The tag on the screen is not linked

Check the tag mapping making sure

 

correctly.

the target device (PLC, etc.) register

 

 

is correct.

 

 

 

 

 

Check the primitive Data Source in

 

 

the user interface in case the word

 

 

WAS is displayed. Re-link the tag in

 

 

this case.

 

 

 

Value shows +BIG or –BIG.

Not enough digits before the decimal

Increase the number of digits before

 

point to show the number. For exam-

the decimal point in the tag format.

 

ple, data is 1000.5 and format is

 

 

three digits before the decimal point

 

 

and one after.

 

 

 

 

Value deviates by a factor of ten.

The tag format is not correct.

Change the decimal point position in

 

 

the tag format.

 

 

 

Value is invalid.

Incorrect tag type.

Check if the tag type corresponds to

 

 

the data type. Is the data a floating

 

 

point number and thus the tag a real

 

 

(Pi symbol), and not an integer (X

 

 

symbol)?

 

 

 

 

Incorrect data mapping.

Check if the tag is accessing the cor-

 

 

rect target device register.

 

 

 

 

Incorrect primitive on the display.

Check if the primitive corresponds to

 

 

the tag type. For example, primitive is

 

 

a Text Integer so the tag has to be an

 

 

integer.

 

 

 

 

Data received is not what’s expected.

Use the transform property on the tag

 

For example, bytes reversed in the

to modify the data source. You might

 

word.

have to try multiple solutions to solve

 

 

the issue.

 

 

 