Troubleshooting

Troubleshooting

NOTE: This section covers the most common problems encountered while setting up, programming or using the product. Do not forget to always download in the device after changing settings in Graco Gateway.

General Troubleshooting

PROBLEM

CAUSE

SOLUTION

 

 

 

 

 

 

Unit screen is blank and PWR LED is

No power applied to the unit.

Check power supply. Units require 24

off.

 

VDC, ± 10%.

 

 

 

Unit screen is blank and PWR LED is

Contrast too low (Graco Gateway

Program one of the soft keys with the

on.

only).

action as User Defined and the fol-

 

 

lowing code in the field On Pressed:

 

 

dispcontrast++

 

 

 

 

No primitives on the display.

Add objects to the User Interface in

 

 

Graco Gateway.

 

 

 

 

Backlight is off.

Push one of the soft keys to turn it

 

 

back on.

 

 

 

 

Backlight tube is broken.

Replace the backlight tube.

 

 

 

Unit continually cycles on and off.

Cross-references between tags, e.g.,

Remove one of the references or use

 

Var1 uses Var2 as maximum which in

formula tags for indirect reference,

 

turn uses Var1 as minimum.

e.g., Form1 is equal to Var1 and used

 

 

in Var2 minimum instead of Var1.

 

 

 

 

Database is corrupted.

Create a new database or send to

 

 

technical support for debugging.

 

 

 

Unit cycles power after an operation.

Most likely a program going in an

Check if the operation launches pro-

 

endless loop.

gram containing loops with no exit

 

 

point.

 

 

 

CF LED flashing slowly.

CF card corrupted or invalid.

Format the card from Graco Gateway

 

 

using the Link > Format Flash menu.

 

 

 

32

312785C

Page 32
Image 32