5 CONTROL PANEL
GE
5.1CONTROL PANEL
Fig.
5.2TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL
inverter on/off
Key to switch the Inverter ON.
(This key is also used to reset “total off” if pressed simultaneously with total off push button).
inverter on/off
Key for Inverter shutdown.
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.
mute
Key to reset general alarm and buzzer.
test | Key to test the control panel LED’s and buzzer. |
| (Pressing this key causes all the LED’s to light and the buzzer to |
| sound 3 times). |
The
By pressing it, you immediately separate the UPS from utility and the Load.
Attention: “total off” cannot disconnect the UPS from the Load with Q2 closed.
To reset “total off”: push and hold the “total off”
For parallel system, pressing “total off” on one unit connected on parallel bus (switch Q1 closed), all the units are separated from the load.
The “total off” reset must be done only on one unit connected on the parallel bus (switch Q1 closed).
Special care must be taken in using this command, in order to avoid accidental Load disconnection.