g

GE

Load on phases screen 2

This screen displays for each phase:

The Load active power (kW) (for RPA: total value of Parallel System).

The Load apparent power (kVA) (for RPA: total value of Parallel System).

metering

LOAD ON PHASES

+

alarms

L1= 6.72kW

8.40kVA

L2= 5.84kW

7.30kVA

parameters

L3= 6.08kW

7.60kVA

ok

 

 

 

 

 

 

Miscellaneous screen

This screen displays:

The temperature of the Inverter Bridge.

The total operating time for the UPS (in hours).

The total operating time for the Inverter (in hours).

metering

MISCELLANEOUS

+

alarms

InvHeatsink =

45°C

UpsOperTime=

3125h

parameters

InvOperTime =

2135h

ok

 

 

 

 

 

 

Utility Faults Statistics screen

This screen displays:

The total number of minor Utility faults (Bypass Utility out of tolerance faults).

The total number of major Utility faults (Rectifier Utility out of tolerance faults).

The total number of detected output overloads.

metering

UTILITY FAULTS STAT.

+

alarms

Minor

=

43210

Major

=

11267

parameters

Overloads=

654

ok

 

 

 

 

 

 

 

 

UPS identification screen

This screen displays:

The UPS family and the power range.

The software version.

The serial number.

metering

UPS IDENTIFICATION

+

alarms

SG Series S0 30kVA

SW Version: x.xx

parameters

S/N: P0030-2003-0001

ok

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

25/88

Operating Manual SG Series 10, 20, 30 & 40 kVA