7.2.3 Restore to normal operation after “total off”
View of the panel after pressing the button “total off”.
•All Contacts are open;
•Rectifier, Inverter and
1.Reset “total off” by pressing and holding the “total off” button and the “inverter on” ( I ) key simultaneously until the Rectifier starts.
2.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
3.Press “inverter on” ( I ) key.
•
•At the end of
•UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status “LOAD ON INVERTER”.
End of procedure