g
GE
7.2PROCEDURES FOR UPS FUNCTIONING AS FREQUENCY CONVERTER
When the SG Series functions as a Frequency Converter, the Automatic Bypass and Manual Bypass functions are disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shutdown for maintenance purposes, also the Load must be shutdown or disconnected
7.2.1
Verify with open front door: Switch Q1 must be open (Pos. O).
1.Connect the Utility power on the UPS.
•Power supply starts up.
Indicated with flashing alarm and buzzer sound.
•LED’s as indicated will be lit.
•Press mute, to reset alarm and buzzer.
2.Close Q1 (Pos. I).
•Rectifier starts automatically, blinking LED indicates
•At the end of Rectifier
3.Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of External Battery.
4.Press “inverter on” ( I ) key.
•
•At the end of
•UPS output LED indicates Load on Inverter.
The LCD must display on the main screen the status “LOAD ON INVERTER”.
End of procedure
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in the case of a Utility Failure.
OPM_SGS_USM_10K_40K_0US_V010.doc | 49/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |