g

GE

 

Code

 

 

Alarms

 

 

Meaning

 

 

 

 

 

 

 

 

 

4404

 

 

K6 CLOSING

 

 

K6 open despite a closing command being issued.

 

 

 

FAILURE

 

 

Signaled by auxiliary contact.

 

 

 

 

 

 

 

The Load cannot be supplied by Automatic Bypass.

 

4405

 

 

K6 OPENING

 

 

K6 closed despite an opening command being issued.

 

 

 

FAILURE

 

 

Signaled by auxiliary contact.

 

 

 

 

 

 

 

 

 

 

SSM

 

 

A faulty current has been detected in the static-switch causing

 

4406

 

 

 

 

the opening of the contactor K6 for 10 sec.

 

 

 

FAILURE

 

 

After 3 times K6 remains definitively open.

 

 

 

 

 

 

 

 

 

 

 

 

 

The alarm reset can be done only from Service.

 

4408

 

 

K8 CLOSING

 

 

K8 not closed despite a closing command being issued.

 

 

 

 

 

Signaled by auxiliary contact.

 

 

 

FAILURE

 

 

 

 

 

 

 

 

The Load cannot be supplied by Automatic Bypass.

 

 

 

 

 

 

 

 

4409

 

 

K8 OPENING

 

 

K8 closed despite an opening command being issued.

 

 

 

FAILURE

 

 

Signaled by auxiliary contact.

 

 

 

 

 

 

 

4410

 

 

BYPASS UTILITY

 

 

The Utility Bypass Voltage is out of the tolerances (± 10%).

 

 

 

 

 

K6 opens, synchronization with Utility is inhibited and transfer

 

 

 

OUT OF TOLERANCE

 

 

 

 

 

 

 

 

to Utility is blocked.

 

 

 

 

 

 

 

 

 

 

 

K3 CLOSING

 

 

K3 open despite a closing command.

 

4420

 

 

 

 

Inverter is switched OFF.

 

 

 

FAILURE

 

 

It can be restarted manually after recovery of the alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

condition.

 

4421

 

 

K3 OPENING

 

 

K3 not open despite an opening command.

 

 

 

FAILURE

 

 

Be aware the DC Capacitors could remain charged.

 

 

 

 

 

 

 

4520

 

 

NO INVERTER

 

 

The Load supplied by Utility exceeds the Inverter power.

 

 

 

POWER

 

 

The Load remains supplied by Utility until the alarm stays ON.

 

 

 

 

 

 

 

4522

 

 

FAN

 

 

A malfunction on the UPS ventilation system was detected.

 

 

 

 

 

No change for UPS operation.

 

 

 

FAILURE

 

 

 

 

 

 

 

 

Call immediately Service Center for intervention.

 

 

 

 

 

 

 

 

 

 

 

LOAD LOCKED

 

 

Load is locked on Utility because 3 transfers on Utility have

 

4530

 

 

 

 

been detected in a short time (default 30 sec.).

 

 

 

ON UTILITY

 

 

The transfer will be free after a time defined in parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

(default 30 sec.).

 

4531

 

 

LOAD ON UTILITY BY

 

 

Load is transferred to Utility because the error detector

 

 

 

ERROR DETECTOR

 

 

detected a disturbance on the output voltage.

 

 

 

 

 

 

 

 

 

 

EMERGENCY OFF

 

 

Alarm after detection of an EPO from an external safety

 

4563

 

 

 

 

device connected on Customer Interface Board.

 

 

 

ACTIVATED

 

 

Consequently K3, K4, K6, K7, K8 open, Rectifier, Inverter and

 

 

 

 

 

 

 

 

 

 

 

 

 

SSM are switched Off.

 

 

 

 

 

 

 

The UPS-System is in an overload condition >125% on

 

4570

 

 

OVERLOAD

 

 

Inverter, or >150% on Utility.

 

 

 

 

 

With Utility unavailable, a sequence of “stop operation” starts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time out depends on Load quantity.

 

 

 

 

 

 

 

With Utility Bypass supply available and load >115%, the

 

4571

 

 

OVERLOAD:

 

 

Load is transferred on Utility.

 

 

 

LOAD ON UTILITY

 

 

Load will be transferred again automatically on Inverter when

 

 

 

 

 

 

 

 

 

 

 

 

 

Load <100%.

 

4581

 

 

INVERTER AND

 

 

The voltages of Utility and Inverter are not synchronized,

 

 

 

UTILITY NOT SYNCH.

 

 

which causes the opening of K6.

 

 

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

37/88