6.6.2Messages list
| Code |
|
| Message |
|
|
| Meaning |
|
|
|
|
|
|
|
|
|
| |
|
|
|
| WATCHDOG |
|
| The microprocessor has detected an incorrect operation: |
| |
| 4002 |
|
|
|
| Transfers the Load on Utility and performs a program reset. |
| ||
|
|
| RESET |
|
| The Inverter will restart automatically and will supply the |
| ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| Load. |
| |
| 4111 |
|
| RECTIFIER |
|
| Rectifier Input Utility is again within the admitted tolerance |
| |
|
|
| UTILITY OK |
|
| (voltage, frequency and phase). |
| ||
|
|
|
|
|
|
| |||
| 4119 |
|
| BATTERY TEST |
|
| Start of Manual or Automatic Battery Test. |
| |
|
|
| STARTED |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| 4120 |
|
| BATTERY TEST |
|
| End of Manual or Automatic Battery Test. |
| |
|
|
| STOPPED |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| 4161 |
|
| RECTIFIER |
|
| Rectifier started. |
| |
|
|
| ON |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| 4162 |
|
| RECTIFIER |
|
| Rectifier shutdown. |
| |
|
|
| OFF |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| 4163 |
|
| GENERATOR |
|
| Customer Interface (X1 - 11, 22) received a |
| |
|
|
|
|
| signal. |
| |||
|
|
| ON |
|
|
| |||
|
|
|
|
|
| Operating mode depend on setting of Parameters. |
| ||
|
|
|
|
|
|
|
| ||
| 4164 |
|
| GENERATOR |
|
| Customer Interface (X1 - 11, 22) received a |
| |
|
|
|
|
| signal. |
| |||
|
|
| OFF |
|
|
| |||
|
|
|
|
|
| Function Bypass enabled depends on setting of Parameter. |
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Inverter cannot be switched on because one of the following |
| |
|
|
|
|
|
|
| conditions is still present: |
| |
|
|
|
|
|
|
| • | Over Temperature |
|
|
|
|
| INVERTER |
|
| • | Low Battery Voltage |
|
| 4302 |
|
|
|
| • | Inverter Fuses |
| |
|
|
| CANNOT BE |
|
|
| |||
|
|
|
|
| • | Overload |
| ||
|
|
|
| TURNED ON |
|
|
| ||
|
|
|
|
|
| • | K7 opening Failure |
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| • | High Battery Voltage |
|
|
|
|
|
|
|
| • | DC Low |
|
|
|
|
|
|
|
| • | EPO |
|
| 4303 |
|
| INVERTER |
|
| Inverter cannot be switched OFF, because the Load cannot |
| |
|
|
| CANNOT BE |
|
| be switched to Utility (voltage out of tolerance, not synchrony, |
| ||
|
|
|
| TURNED OFF |
|
| BP blocked). |
| |
| 4361 |
|
| INVERTER |
|
| The command to start the Inverter has been activated on the |
| |
|
|
| ON |
|
| control panel. |
| ||
|
|
|
|
|
|
| |||
| 4362 |
|
| INVERTER |
|
| The command to switch OFF the Inverter has been activated |
| |
|
|
| OFF |
|
| by the control panel or automatically for alarm presence. |
| ||
|
|
|
|
|
|
| |||
| 4411 |
|
| BYPASS UTILITY |
|
| Bypass Input Utility is again within tolerance (voltage, |
| |
|
|
| OK |
|
| frequency and phase). |
| ||
|
|
|
|
|
|
| |||
| 4500 |
|
| COMMAND |
|
| Disconnection of the Load by opening K6 and K7 for: |
| |
|
|
| LOAD OFF |
|
| EPO / total off / Overload / stop operation. |
| ||
|
|
|
|
|
|
| |||
| 4521 |
|
| NO BYPASS |
|
| With the Load supplied by Automatic Bypass, a Utility Failure |
| |
|
|
| POWER |
|
| or K6 opening occurred. |
| ||
|
|
|
|
|
|
| |||
| 4534 |
|
| MULTIPLE LOAD |
|
| 2 transfers Inverter- Utility have been detected in a short time, |
| |
|
|
| TRANSFER |
|
| (default 30 sec.). |
| ||
|
|
|
|
|
|
|