Code

 

 

Alarms

 

 

Meaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The Battery has been discharged and reached “stop

 

4115

 

 

LOW BATTERY

 

 

operation” time-out (default 3 minutes), and the Inverter will

 

 

 

 

 

be shut down.

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

It will restart automatically only when the Battery has

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recharged enough for a minimum runtime.

 

4116

 

 

HIGH BATTERY

 

 

Dangerous high DC Voltage caused inverter shutdown.

 

 

 

 

 

Inverter restarts automatically after Battery returns to floating

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

voltage.

 

 

 

 

 

 

 

 

4117

 

 

BATTERY

 

 

A leakage current to earth has been detected on the DC

 

 

 

EARTH FAULT

 

 

circuit.

 

 

 

 

 

 

 

4118

 

 

BATTERY FAULT

 

 

During battery test the voltage falls under the critical level

 

 

 

 

 

(depending setting parameters).

 

 

 

 

 

 

 

Battery test is stopped.

 

 

 

 

TURN ON RECT.

 

 

Rectifier and Inverter are OFF.

 

4130

 

 

 

 

The DC power supply is discharging the Battery.

 

 

 

OR SHUTDOWN UPS

 

 

Rectifier must be restarted or Battery must be disconnected in

 

 

 

 

 

 

 

order to avoid damage.

 

4140

 

 

RECTIFIER

 

 

Rectifier Voltage hasn’t reached the set value (probably fault

 

 

 

CONTROL FAILURE

 

 

on regulation loop). LED Rectifier on control panel is blinking.

 

 

 

 

 

 

 

4301

 

 

INVERTER

 

 

Inverter Output Fuses blown (F5, F6 and F7).

 

 

 

 

 

Inverter can be started manually after replacement of the

 

 

 

FUSES FAILURE

 

 

 

 

 

 

 

 

fuses.

 

 

 

 

 

 

 

 

4304

 

 

K7 CLOSING

 

 

K7 not closed despite a closing command being issued.

 

 

 

 

 

Signaled by auxiliary contact.

 

 

 

FAILURE

 

 

 

 

 

 

 

 

Load will be supplied by Utility.

 

 

 

 

 

 

 

 

4305

 

 

K7 OPENING

 

 

K7 not open despite an opening command being issued.

 

 

 

 

 

Signaled by auxiliary contact.

 

 

 

FAILURE

 

 

 

 

 

 

 

 

Load will be supplied by Utility.

 

 

 

 

 

 

 

 

 

 

 

INVERTER

 

 

The temperature sensor of the Inverter Transformer indicates

 

 

 

 

 

 

over temperature.

 

4307

 

 

TRANSFORMER

 

 

 

 

 

 

 

Elapsed “stop operation” time, Inverter shutdown.

 

 

 

 

OVERTEMPERATURE

 

 

 

 

 

 

 

 

With Utility OK, Load is transferred on Utility.

 

 

 

 

 

 

 

 

4308

 

 

DC FUSES

 

 

Blown input DC fuse(s) F1 of the Inverter.

 

 

 

FAILURE

 

 

Inverter cannot be started as long as present.

 

 

 

 

 

 

 

 

 

 

DRIVER

 

 

An abnormal condition has been detected on one or more

 

4309

 

 

 

 

power modules of the Inverter (temperature or over current).

 

 

 

FAILURE

 

 

Inverter shutdown and cannot be started as long as the alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

is present.

 

4312

 

 

INV. VOLTAGE

 

 

Inverter Output Voltage is out of the tolerances (± 10%).

 

 

 

OUT OF TOLERANCE

 

 

Inverter is switched OFF.

 

 

 

 

 

 

 

 

 

 

ISMAX

 

 

Detection of Inverter Bridge (Is) current limit causing the

 

4320

 

 

 

 

Inverter OFF and automatic re-start.

 

 

 

DETECTION

 

 

After 3 times the Inverter switches-Off, and it can be restarted

 

 

 

 

 

 

 

 

 

 

 

 

 

manually.

 

 

 

 

 

 

 

The “Slave” oscillator is not in synchronized with the Master;

 

 

 

 

INVERTER

 

 

thus causing the shutdown of it’s Inverter.

 

4340

 

 

 

 

If after a restart the condition remains, the LED inside the

 

 

 

CONTROL FAILURE

 

 

 

 

 

 

 

 

Inverter symbol on the panel will not light up, indicating that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

this Inverter cannot supply the Load anymore.

 

 

 

 

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

36/88