| Code |
|
| Alarms |
|
| Meaning |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| The Battery has been discharged and reached “stop |
| 4115 |
|
| LOW BATTERY |
|
| operation” |
|
|
|
|
| be shut down. | ||
|
|
| VOLTAGE |
|
| ||
|
|
|
|
|
| It will restart automatically only when the Battery has | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| recharged enough for a minimum runtime. |
| 4116 |
|
| HIGH BATTERY |
|
| Dangerous high DC Voltage caused inverter shutdown. |
|
|
|
|
| Inverter restarts automatically after Battery returns to floating | ||
|
|
| VOLTAGE |
|
| ||
|
|
|
|
|
| voltage. | |
|
|
|
|
|
|
| |
| 4117 |
|
| BATTERY |
|
| A leakage current to earth has been detected on the DC |
|
|
| EARTH FAULT |
|
| circuit. | |
|
|
|
|
|
| ||
| 4118 |
|
| BATTERY FAULT |
|
| During battery test the voltage falls under the critical level |
|
|
|
|
| (depending setting parameters). | ||
|
|
|
|
|
|
| Battery test is stopped. |
|
|
|
| TURN ON RECT. |
|
| Rectifier and Inverter are OFF. |
| 4130 |
|
|
|
| The DC power supply is discharging the Battery. | |
|
|
| OR SHUTDOWN UPS |
|
| Rectifier must be restarted or Battery must be disconnected in | |
|
|
|
|
|
|
| order to avoid damage. |
| 4140 |
|
| RECTIFIER |
|
| Rectifier Voltage hasn’t reached the set value (probably fault |
|
|
| CONTROL FAILURE |
|
| on regulation loop). LED Rectifier on control panel is blinking. | |
|
|
|
|
|
| ||
| 4301 |
|
| INVERTER |
|
| Inverter Output Fuses blown (F5, F6 and F7). |
|
|
|
|
| Inverter can be started manually after replacement of the | ||
|
|
| FUSES FAILURE |
|
| ||
|
|
|
|
|
| fuses. | |
|
|
|
|
|
|
| |
| 4304 |
|
| K7 CLOSING |
|
| K7 not closed despite a closing command being issued. |
|
|
|
|
| Signaled by auxiliary contact. | ||
|
|
| FAILURE |
|
| ||
|
|
|
|
|
| Load will be supplied by Utility. | |
|
|
|
|
|
|
| |
| 4305 |
|
| K7 OPENING |
|
| K7 not open despite an opening command being issued. |
|
|
|
|
| Signaled by auxiliary contact. | ||
|
|
| FAILURE |
|
| ||
|
|
|
|
|
| Load will be supplied by Utility. | |
|
|
|
|
|
|
| |
|
|
|
| INVERTER |
|
| The temperature sensor of the Inverter Transformer indicates |
|
|
|
|
|
| over temperature. | |
| 4307 |
|
| TRANSFORMER |
|
| |
|
|
|
|
| Elapsed “stop operation” time, Inverter shutdown. | ||
|
|
|
| OVERTEMPERATURE |
|
| |
|
|
|
|
|
| With Utility OK, Load is transferred on Utility. | |
|
|
|
|
|
|
| |
| 4308 |
|
| DC FUSES |
|
| Blown input DC fuse(s) F1 of the Inverter. |
|
|
| FAILURE |
|
| Inverter cannot be started as long as present. | |
|
|
|
|
|
| ||
|
|
|
| DRIVER |
|
| An abnormal condition has been detected on one or more |
| 4309 |
|
|
|
| power modules of the Inverter (temperature or over current). | |
|
|
| FAILURE |
|
| Inverter shutdown and cannot be started as long as the alarm | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| is present. |
| 4312 |
|
| INV. VOLTAGE |
|
| Inverter Output Voltage is out of the tolerances (± 10%). |
|
|
| OUT OF TOLERANCE |
|
| Inverter is switched OFF. | |
|
|
|
|
|
| ||
|
|
|
| ISMAX |
|
| Detection of Inverter Bridge (Is) current limit causing the |
| 4320 |
|
|
|
| Inverter OFF and automatic | |
|
|
| DETECTION |
|
| After 3 times the Inverter | |
|
|
|
|
|
| ||
|
|
|
|
|
|
| manually. |
|
|
|
|
|
|
| The “Slave” oscillator is not in synchronized with the Master; |
|
|
|
| INVERTER |
|
| thus causing the shutdown of it’s Inverter. |
| 4340 |
|
|
|
| If after a restart the condition remains, the LED inside the | |
|
|
| CONTROL FAILURE |
|
| ||
|
|
|
|
|
| Inverter symbol on the panel will not light up, indicating that | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| this Inverter cannot supply the Load anymore. |
|
|
|
|
|
|
|
|
OPM_SGS_USM_10K_40K_0US_V010.doc | 36/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |