7.4.4 Separate a Unit from the parallel system (System Redundancy)
Initial status: Load supplied from all Inverters.
First operated unit | All other units of the system |
1.Press and hold “inverter off” ( O ) key on the Unit, to separate, until the LED turns OFF.
Load supplied from Inverter(s) of the other Unit(s) of the parallel system.
First operated unit | All other units of the system |
2.Open Q1 (Pos. O) and, only when the LED service check is ON, press “total off” button on the Unit to separate.
First operated unit | All other units of the system |
3.Disconnect the Battery from the Unit to separate.
• Wait 5 minutes for
4.Disconnect the Utility supply from separated Unit.
First operated unit | All other units of the system |
End of procedure
For any further intervention could nearest Service Center.