6.6EVENTS (ALARMS AND MESSAGES)
Each of the following listed events can be displayed on the LCD screen or on PC where the ARGUS/JumpManager - Control Network is installed.
Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the UPS (which are additionally signaled with the LED alarm and acoustically with the buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list, but no activating the LED alarm and the buzzer).
When in the alarms mode, the LCD screen displays a time ordered sequence of screens corresponding to the last 256 alarms and messages, each screen indicating:
The number of the event (255 = the most recent). The date and time when the event occurred.
The standard code and the status word. An explicit text description of the events.
6.6.1Alarms list
| Code |
|
| Alarms |
|
| Meaning |
|
|
|
|
|
|
|
|
|
|
| 4000 |
|
| SETUP VALUES |
|
| Parameters are lost and have been replaced with | default |
|
|
|
|
| values. |
| ||
|
|
| LOST |
|
|
| ||
|
|
|
|
|
| Call nearest Service Center for intervention. |
| |
|
|
|
|
|
|
|
| |
| 4004 |
|
| UPS |
|
| The master unit detected the slave unit missing | on the |
|
|
| FAILURE |
|
| communication bus even though switch Q1 is still closed. | ||
|
|
|
|
|
| |||
| 4100 |
|
| RECTIFIER FUSES |
|
| The | |
|
|
|
|
| a blown fuse, and consequently shut down. |
| ||
|
|
| FAILURE |
|
|
| ||
|
|
|
|
|
| Clearance of this condition allows you to restart the Rectifier. | ||
|
|
|
|
|
|
| ||
| 4102 |
|
| K4 CLOSING |
|
| K4 not closed despite a closing command being issued. | |
|
|
|
|
| Signaled by auxiliary contact. |
| ||
|
|
| FAILURE |
|
|
| ||
|
|
|
|
|
| Rectifier cannot start. |
| |
|
|
|
|
|
|
|
| |
| 4103 |
|
| K4 OPENING |
|
| K4 not open despite an opening command being issued. | |
|
|
|
|
| Signaled by auxiliary contact. |
| ||
|
|
| FAILURE |
|
|
| ||
|
|
|
|
|
| Utility remains connected to Rectifier bridge. |
| |
|
|
|
|
|
|
|
| |
|
|
|
| BATTERY |
|
| This function, when enabled on input programmable relays | |
| 4104 |
|
|
|
| (password required), warns the user about the | external | |
|
|
| FUSES |
|
| Battery Fuses failure or MCB opening, signalled by NO free | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
| contact. |
|
|
|
|
|
|
|
| Temperature sensor indicates an over temperature on the | |
| 4105 |
|
| RECTIFIER |
|
| Rectifier Bridge. |
|
|
|
|
|
| Only alarm is given. |
| ||
|
|
| OVERTEMPERATURE |
|
|
| ||
|
|
|
|
|
| The Rectifier, when in Off state, cannot start as long as this | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| condition persists. |
|
|
|
|
|
|
|
| The temperature sensor inside the input transformer winding | |
| 4106 |
|
| RECTIFIER |
|
| indicates over temperature. |
|
|
|
| TRANSFORMER |
|
| Only the alarm is given. |
| |
|
|
|
| OVERTEMPERATURE |
|
| The Rectifier, when in Off state, cannot start as long as this | |
|
|
|
|
|
|
| condition persists. |
|
| 4110 |
|
| RECTIFIER UTILITY |
|
| Rectifier Input Utility is out of tolerance (voltage, frequency or | |
|
|
| OUT OF TOLERANCE |
|
| phase). |
| |
|
|
|
|
|
|
|
OPM_SGS_USM_10K_40K_0US_V010.doc | 35/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |