g

GE

 

Code

 

 

Message

 

 

 

 

Meaning

 

 

 

 

 

 

 

 

 

 

 

4535

 

 

BYPASS

 

 

Bypass is not available.

 

 

 

 

 

LOCKED

 

 

Contactor K6 and K8 are open, SSM deactivated.

 

 

4536

 

 

BYPASS

 

 

Bypass is enabled.

 

 

 

 

FREE

 

 

Contactor K6 is closed.

 

 

 

 

 

 

 

 

 

4561

 

 

TOTAL

 

 

Push-button “total off” on the UPS Control Panel has been

 

 

 

 

OFF

 

 

pressed, with the output circuit switch Q1 closed.

 

 

 

 

 

 

 

 

 

4562

 

 

DETOUR

 

 

The auxiliary contact indicates that Manual Bypass Q2 was

 

 

 

 

ON

 

 

closed.

 

 

 

 

 

 

 

 

 

4564

 

 

DETOUR

 

 

The auxiliary contact indicates that Manual Bypass Q2 was

 

 

 

 

OFF

 

 

opened.

 

 

 

 

 

 

 

 

 

4567

 

 

COMMAND

 

 

The control unit received a command to transfer the Load on

 

 

 

 

LOAD ON UTILITY

 

 

Utility.

 

 

 

 

 

 

 

 

 

 

 

4568

 

 

COMMAND

 

 

The control unit received a command to transfer the Load on

 

 

 

 

LOAD ON INVERTER

 

 

Inverter.

 

 

 

 

 

 

 

 

 

4572

 

 

NO MORE

 

 

End of the overload condition detected with alarm 4570.

 

 

 

 

OVERLOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4580

 

 

INVERTER AND

 

 

The voltages of Inverter and Utility Bypass are synchronized.

 

 

 

 

UTILITY

 

 

 

 

 

 

 

 

 

 

SYNCHRONIZED

 

 

 

 

 

 

 

4582

 

 

COMMAND

 

 

Command not to synchronize with Utility.

 

 

 

 

NOT TO

 

 

 

 

 

 

 

 

 

 

SYNCHRONIZE

 

 

 

 

 

 

 

4583

 

 

COMMAND TO

 

 

Command to synchronize with Utility.

 

 

 

 

SYNCHRONIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4602

 

 

Q1

 

 

The auxiliary contact indicates that the output switch Q1 was

 

 

 

 

OPEN

 

 

opened.

 

 

 

 

 

 

 

 

 

4603

 

 

Q1

 

 

The auxiliary contact indicates that the output switch Q1 was

 

 

 

 

CLOSED

 

 

closed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic Battery Test is not possible due to:

 

 

4699

 

 

BATTERY TEST

 

 

No Utility Rectifier or Bypass.

 

 

 

 

 

 

Battery not fully charged.

 

 

 

 

IMPOSSIBLE

 

 

 

 

 

 

 

 

 

Load is below 10% or above 80%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test is postponed for 1 week.

 

 

 

 

 

 

 

 

Inverter can be started or shutdown by remote control.

 

 

 

 

 

 

 

 

Commands source can be chosen depending on the value of

 

 

4763

 

 

REMOTE CONTROL

 

 

parameter (Service only):

 

 

 

 

ON

 

0

=

Only local panel.

 

 

 

 

 

 

 

 

 

 

 

 

 

1

=

Only serial port on CI.

 

 

 

 

 

 

 

2

=

Both.

 

 

 

 

 

 

 

 

Inverter cannot be started or shutdown by remote control.

 

 

 

 

 

 

 

 

Commands source can be chosen depending on the value of

 

 

4764

 

 

REMOTE CONTROL

 

 

parameter (Service only):

 

 

 

 

OFF

 

0

=

Only local panel.

 

 

 

 

 

 

 

1

=

Only serial port on CI.

 

 

 

 

 

 

 

2

=

Both.

 

 

 

 

 

 

 

 

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

40/88

Operating Manual SG Series 10, 20, 30 & 40 kVA