g
GE
| Code |
|
| Message |
|
|
|
| Meaning |
|
|
|
|
|
|
|
|
|
| ||
| 4535 |
|
| BYPASS |
|
| Bypass is not available. |
| ||
|
|
|
| LOCKED |
|
| Contactor K6 and K8 are open, SSM deactivated. |
| ||
| 4536 |
|
| BYPASS |
|
| Bypass is enabled. |
| ||
|
|
| FREE |
|
| Contactor K6 is closed. |
| |||
|
|
|
|
|
|
| ||||
| 4561 |
|
| TOTAL |
|
|
| |||
|
|
| OFF |
|
| pressed, with the output circuit switch Q1 closed. |
| |||
|
|
|
|
|
|
| ||||
| 4562 |
|
| DETOUR |
|
| The auxiliary contact indicates that Manual Bypass Q2 was |
| ||
|
|
| ON |
|
| closed. |
| |||
|
|
|
|
|
|
| ||||
| 4564 |
|
| DETOUR |
|
| The auxiliary contact indicates that Manual Bypass Q2 was |
| ||
|
|
| OFF |
|
| opened. |
| |||
|
|
|
|
|
|
| ||||
| 4567 |
|
| COMMAND |
|
| The control unit received a command to transfer the Load on |
| ||
|
|
| LOAD ON UTILITY |
|
| Utility. |
|
| ||
|
|
|
|
|
|
|
| |||
| 4568 |
|
| COMMAND |
|
| The control unit received a command to transfer the Load on |
| ||
|
|
| LOAD ON INVERTER |
|
| Inverter. |
| |||
|
|
|
|
|
|
| ||||
| 4572 |
|
| NO MORE |
|
| End of the overload condition detected with alarm 4570. |
| ||
|
|
| OVERLOAD |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| 4580 |
|
| INVERTER AND |
|
| The voltages of Inverter and Utility Bypass are synchronized. |
| ||
|
|
| UTILITY |
|
|
|
|
|
| |
|
|
|
| SYNCHRONIZED |
|
|
|
|
|
|
| 4582 |
|
| COMMAND |
|
| Command not to synchronize with Utility. |
| ||
|
|
| NOT TO |
|
|
|
|
|
| |
|
|
|
| SYNCHRONIZE |
|
|
|
|
|
|
| 4583 |
|
| COMMAND TO |
|
| Command to synchronize with Utility. |
| ||
|
|
| SYNCHRONIZE |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| 4602 |
|
| Q1 |
|
| The auxiliary contact indicates that the output switch Q1 was |
| ||
|
|
| OPEN |
|
| opened. |
| |||
|
|
|
|
|
|
| ||||
| 4603 |
|
| Q1 |
|
| The auxiliary contact indicates that the output switch Q1 was |
| ||
|
|
| CLOSED |
|
| closed. |
| |||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Automatic Battery Test is not possible due to: |
| ||
| 4699 |
|
| BATTERY TEST |
|
| • No Utility Rectifier or Bypass. |
| ||
|
|
|
|
| • Battery not fully charged. |
| ||||
|
|
| IMPOSSIBLE |
|
|
| ||||
|
|
|
|
|
| • Load is below 10% or above 80%. |
| |||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| Test is postponed for 1 week. |
| ||
|
|
|
|
|
|
| Inverter can be started or shutdown by remote control. |
| ||
|
|
|
|
|
|
| Commands source can be chosen depending on the value of |
| ||
| 4763 |
|
| REMOTE CONTROL |
|
| parameter (Service only): |
| ||
|
|
| ON |
| 0 | = | Only local panel. |
| ||
|
|
|
|
|
| |||||
|
|
|
|
|
| 1 | = | Only serial port on CI. |
| |
|
|
|
|
|
| 2 | = | Both. |
| |
|
|
|
|
|
|
| Inverter cannot be started or shutdown by remote control. |
| ||
|
|
|
|
|
|
| Commands source can be chosen depending on the value of |
| ||
| 4764 |
|
| REMOTE CONTROL |
|
| parameter (Service only): |
| ||
|
|
| OFF |
| 0 | = | Only local panel. |
| ||
|
|
|
|
|
| 1 | = | Only serial port on CI. |
| |
|
|
|
|
|
| 2 | = | Both. |
| |
|
|
|
|
|
|
|
|
|
|
|
OPM_SGS_USM_10K_40K_0US_V010.doc | 40/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |