g

GE

Rectifier Utility data screen

This screen refers to the AC source supplying the Rectifier.

This screen displays:

Iout1 = output current Rectifier Bridge.

Iout2 = output current 2nd Rectifier Bridge (optional 12 pulse Rectifiers only).

The voltage levels between the three phases (line-to-line).

The input frequency of the Rectifier.

metering

RECTIFIER

+

alarms

U12=481V

Iout1 =107A

U23=480V

Iout2 = 0A

parameters

U31=482V

f=60.0Hz

ok

 

 

 

 

 

 

Inverter data screen

This screen displays:

The voltage level of the three phase voltages (line-to-neutral).

The output frequency of the Inverter.

The synchronization status of the Inverter with respect to Utility.

metering

INVERTER:

U1=277V

+

alarms

U2= 277V

U3=277V

Frequency = 60.0Hz

parameters

Synchronized

ok

 

 

 

 

 

 

Status Load screen

This screen displays:

The Load level in kVA (for RPA: only this unit).

The Load level as a percentage of the nominal rated Load (for RPA: only this unit).

The source of the power supplied to the Load.

metering

 

LOAD ON UPS

+

alarms

Load

=

25.20kVA

Percentage =

84%

parameters

LOAD ON INVERTER

ok

 

 

 

Load on phases screen 1

This screen displays for each phase:

The output phase voltage and current as RMS values (for RPA: total value of Parallel System).

The output Load as percent (for RPA: respect to the rated power of Parallel System).

metering

alarms parameters

LOAD ON PHASES U1=277V I=30A 84% U2=277V I=26A 73% U3=277V I=27A 76%

+

ok

OPM_SGS_USM_10K_40K_0US_V010.doc

24/88

Operating Manual SG Series 10, 20, 30 & 40 kVA