g
GE
7.3.5 Reconnect a Unit to a parallel system
1.Connect the Utility supply on the separated Unit.
• Press mute, to reset alarm and buzzer.
First operated unit | All other units of the system |
2.Close Q1 (Pos. I) on the separated Unit. Rectifier starts automatically.
First operated unit | All other units of the system |
3.Connect the Battery, in case of External Battery, to the UPS on the separated Unit by closing the external Battery Switch or Fuses.
4.Press “inverter on” ( I ) key on the separated Unit.
After
• The LCD must display on the main screen the status “LOAD ON INVERTER”.
First operated unit | All other units of the system |
End of procedure
OPM_SGS_USM_10K_40K_0US_V010.doc | 59/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |