| Code |
|
| Alarms |
|
| Meaning |
|
|
|
|
|
|
|
|
| 4697 |
|
| BATTERY |
|
| Detection of Battery over temperature condition. |
|
|
|
| OVERTEMPERATURE |
|
| Can be deactivated by Service. |
| 4698 |
|
| BATTERY POWER |
|
| In case of Utility Failure, with the actual Load, the run time |
|
|
| INSUFFICIENT |
|
| would be below stop operation time (default 3 minutes). | |
|
|
|
|
|
| ||
| 4700 |
|
|
|
|
| Battery voltage is at the lowest limit. |
|
|
| DC LOW |
|
| Will stay Off inverter until the battery voltage reaches the | |
|
|
|
|
|
|
| value in parameter. |
| 4900 |
|
| LOAD LOCKED |
|
| The Load is locked on Inverter after 3 Load transfers within 30 |
|
|
|
|
| seconds. | ||
|
|
| ON INVERTER |
|
| ||
|
|
|
|
|
| After time out (default 30 sec.) Bypass will be free. | |
|
|
|
|
|
|
| |
| 4955 |
|
|
|
|
| An |
|
| OVERTEMPERATURE |
|
| Elapsed “stop operation” time, Inverter shutdown. | ||
|
|
|
|
|
|
| With Utility OK, Load is transferred on Utility. |
| 4998 |
|
| LOAD OFF DUE TO |
|
| Load Off after |
|
|
| EXTENT. OVERLOAD |
|
| Inverter or Bypass (time depending on the % of overload). | |
|
|
|
|
|
| ||
| 4999 |
|
| LOAD OFF DUE |
|
| Load Off after |
|
| TO UBATT. OR TEMP. |
|
| due to Battery low voltage or | ||
|
|
|
|
|
|
|
|