g

GE

 

Code

 

 

Alarms

 

 

Meaning

 

 

 

 

 

 

 

 

 

4697

 

 

BATTERY

 

 

Detection of Battery over temperature condition.

 

 

 

 

OVERTEMPERATURE

 

 

Can be deactivated by Service.

 

4698

 

 

BATTERY POWER

 

 

In case of Utility Failure, with the actual Load, the run time

 

 

 

INSUFFICIENT

 

 

would be below stop operation time (default 3 minutes).

 

 

 

 

 

 

 

4700

 

 

 

 

 

Battery voltage is at the lowest limit.

 

 

 

DC LOW

 

 

Will stay Off inverter until the battery voltage reaches the

 

 

 

 

 

 

 

value in parameter.

 

4900

 

 

LOAD LOCKED

 

 

The Load is locked on Inverter after 3 Load transfers within 30

 

 

 

 

 

seconds.

 

 

 

ON INVERTER

 

 

 

 

 

 

 

 

After time out (default 30 sec.) Bypass will be free.

 

 

 

 

 

 

 

 

4955

 

 

 

 

 

An over-temperature condition has been detected on Inverter.

 

 

OVERTEMPERATURE

 

 

Elapsed “stop operation” time, Inverter shutdown.

 

 

 

 

 

 

 

With Utility OK, Load is transferred on Utility.

 

4998

 

 

LOAD OFF DUE TO

 

 

Load Off after time-out of “stop operation” for overload on

 

 

 

EXTENT. OVERLOAD

 

 

Inverter or Bypass (time depending on the % of overload).

 

 

 

 

 

 

 

4999

 

 

LOAD OFF DUE

 

 

Load Off after time-out of “stop operation” with missing Utility

 

 

TO UBATT. OR TEMP.

 

 

due to Battery low voltage or over-temperature condition.

 

 

 

 

 

 

 

 

OPM_SGS_USM_10K_40K_0US_V010.doc

38/88

Operating Manual SG Series 10, 20, 30 & 40 kVA