7.3.2 Maintenance system shutdown (Load supplied from Q2 on all Units)

Initial status: Load supplied from all Inverters.

 

First operated unit

All other units of the system

 

 

1.

Press inverter off( O ) key on all Units, and hold until the LED inside the Inverter

 

symbol turns OFF.

 

 

At no redundancy, the system will transfer to Utility supply.

 

First operated unit

All other units of the system

 

 

 

2.

Close Q2 (Pos. I) on all Units.

 

 

Load is now supplied from Utility in parallel from Bypass and Manual Bypass Q2 of all Units.

 

First operated unit

All other units of the system

 

 

3.

Open Q1 (Pos. O) and then press total offbutton on all Units.

 

The Bypass of all Units will disconnect and all Rectifiers are shutdown.

 

First operated unit

All other units of the system

 

 

4.

Disconnect the Battery, in case of External Battery, from all Units.

 

Wait 5 minutes for DC-Link Capacitors discharge.

 

 

First operated unit

All other units of the system

 

 

 

 

End of procedure

 

OPM_SGS_USM_10K_40K_0US_V010.doc

55/88

Operating Manual SG Series 10, 20, 30 & 40 kVA