9.4CONNECTION FOR OPTIONS

The installation and cabling of the options must be performed a qualified service person.

9.4.1 Remote Signaling Box (RSB)

The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential free contacts fitted on the P4 - Customer Interface Boardof the UPS.

It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be surface mounted.

The remote panel contains an internal buzzer and the following status indicators:

Mimic diagram with LED's indicating the operation of Rectifier and Inverter, and the power source supplying the critical Load.

Alarm

(LED light and audible alarm) indicating a critical situation on the UPS.

Stop

indicating the UPS is preparing to shut down in a short time.

Mute

push button to reset the buzzer.

Test

push button checks all the LED’s and the buzzer of the remote panel.

The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm2.

The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included). Maximal admitted length: 985 ft (300 m).

It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board).

The alarms on free potential contacts can be connected on terminals X1 instead J2 (see correlation X1 – J2 in chapter 8.1).

XA

 

 

pink

 

 

 

A

 

 

red

 

 

REMOTE

TERMINALS

grey

 

 

SIGNALLING

blue

 

 

BLOCK

 

 

 

BOX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

red pink

 

IM6544

 

25

 

 

blue grey

24V

1

 

 

 

X15

 

 

 

GND

 

24

 

 

 

2

 

23

 

 

 

UTILITY FAILURE

31

 

 

22

 

 

 

32

 

 

white

 

 

 

 

 

21

 

 

 

33

 

MALE

20

brown

 

 

 

34

 

19

green

 

 

 

37

 

18

yellow

 

 

 

38

 

-

17

 

 

 

 

40

 

D

16

 

 

 

 

 

black

 

 

 

42

X4

- SUB

15

violet

 

 

LOAD ON INVERTER

43

14

 

 

 

44

 

13

 

 

 

 

 

J2

12

 

 

 

LOAD ON MAINS

49

 

11

 

 

 

50

 

-

 

 

 

 

 

10

 

 

 

 

55

 

 

9

 

 

 

 

56

 

12

1

13

2

14

3

15

4

16

5

17

6

18

7

19

8

20

9

21

10

22

11

1

 

2

 

J2

14

1

9

1

P4 - IM0005 Customer Interface

 

 

Pink + Red

XA

1

XA

2

 

 

TERMINALS BLOCK

 

 

Grey + Blue

1

 

J2

2

 

3

 

B PLUG

4

 

SUB D - MALE

 

 

1

 

/ 300m

 

985ft

2

 

3

 

max

4

 

 

A

B

8

grey/pink

 

 

 

 

blue/red

 

 

 

 

7

 

 

 

 

 

 

 

 

 

6

white/green

 

16

 

 

5

COMMON ALLARM

 

 

brown/green

17

 

 

4

 

 

 

white/yellow

 

19

X3

 

3

AUX. BUZZER

 

yellow/brown

20

 

2

 

STOP OPERATION

22

 

 

1

 

 

 

 

23

 

 

 

 

 

 

P.S.: The above mentioned colors are suitables only for XY standard cable

 

 

 

S

 

in

 

U

 

m

1

 

3

_

 

7m

0

 

S

 

7

 

M

 

 

 

R

 

 

 

_

 

 

 

0

 

 

 

5

 

 

 

1

 

 

 

-

 

 

 

0

 

Stop

 

1

1/4"5 in 130mm

 

0

 

 

_

 

0

 

Alarm

 

T

 

 

P

 

 

 

O

 

 

 

_

 

 

 

0

 

 

0

 

 

5

 

 

T

g

Mute Test

G

S

 

GE Digital Energy

 

 

8 1/2" in 216mm

Fig. 8.4.1-1 Remote Signaling Box connection

ATerminals X3, X4 and X15 fitted inside the Remote Signaling Box.

BPlug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female- 25 pin) located on P4 - Customer Interface Board.

XA Terminals block XA for 24 VDC / 1A supply Remote Signaling Box.

If the remote signal panel is plugged on connector J2, the terminal blocks X1 cannot be used to drive an external alarms monitoring device, because it is supplied by the internal UPS low voltage power supply.

OPM_SGS_USM_10K_40K_0US_V010.doc

84/88

Operating Manual SG Series 10, 20, 30 & 40 kVA