g
GE
7.3PROCEDURES FOR PARALLEL SYSTEM
7.3.1 Parallel System
Verify on all Units, with open front door: Switches Q1 and Q2 must be open (Pos. O).
1.Connect the Utility power on all UPS’s.
(In case of separate inputs for Rectifier and Bypass, connect both).
•Power supply starts up. Indicated with flashing alarm and buzzer sounds.
•LED’s as indicated will be lit.
•Press mute, to reset alarm and buzzer.
First operated unit | All other units of the system |
2.Close Q1 (Pos. I) on all Units.
•When closing Q1 on the last unit of the parallel system, the Bypass of all Units connects to the Load.
•Rectifiers start automatically, blinking LED indicates
•At the end of Rectifier
•LED’s service check turn OFF.
First operated unit | All other units of the system |
3.Connect the Battery to all Units by closing the external Battery Switches or Fuses, in case of External Battery.
Continue ►
OPM_SGS_USM_10K_40K_0US_V010.doc | 53/88 | Operating Manual SG Series 10, 20, 30 & 40 kVA |