7.4.5 Reconnect a Unit to a parallel system
1.Connect the Utility supply on the separated Unit.
• Press mute, to reset alarm and buzzer.
First operated unit | All other units of the system |
2.Connect the Battery to the UPS separated by closing the external Battery Switch or Fuses.
3.Close Q1 (Pos. I) on the separated Unit. Rectifier starts automatically.
First operated unit | All other units of the system |
4.Press “inverter on” ( I ) key on the separated Unit.
After
First operated unit | All other units of the system |
End of procedure