DIAGNOSTIC STATUS CODES

TRANSISTOR PUMP CONTROL

Page 46

Section 4.7 Pump Control Codes

 

PUMP

DESCRIPTION OF STATUS

CAUSE OF STATUS INDICATION

STATUS CODE

 

 

 

 

 

-117

“Card Type” selection is invalid.

This status code will be displayed when the card type

 

selection value is set to an invalid number.

 

 

 

MEMORY RECALL

CORRECTIVE ACTIONS

TROUBLE-SHOOTING DIAGRAM

NO

 

 

 

SYMPTOM

 

Circuits valid

Control will not operate.

NO

for

POSSIBLE CAUSE

Pump

GRAPHIC

Invalid card type selection.

Controller

Review function 17 in the Handset

FOR THIS

 

Instruction sheets. Adjust and set

 

card type value as instructed by OEM

 

service manual.

STATUS CODE

 

 

 

Verify that the correct logic card

 

 

catalog number is installed in the

 

 

controller.

 

 

 

 

PUMP

DESCRIPTION OF STATUS

STATUS CODE

 

-127

Control logic card power supply is less

than 10 VDC.

MEMORY RECALL

CORRECTIVE ACTIONS

YES

Circuits valid

SYMPTOM

Control will not operate.

CAUSE OF STATUS INDICATION

This status code is displayed when the logic card power supply is less than 10 volts.

TROUBLE-SHOOTING DIAGRAM

FU3

KEY SWITCH

 

 

 

for

POSSIBLE CAUSE

Pump

Controller

Discharged Battery

 

Check battery to insure proper state of

 

charge.

Loose connection at P1.

Insure that the wire connection at P1 is tight.

Defective logic card

Replace control.

FU2

LINE FU1

+

-

P1 P2

POS

A1

FIELD

POWER CONNECTIONS

ARMATURE

NEG

A2

 

January 2000

Page 46