Hardwire Zones and Zone Expansion

Installation and Setup Guide

Hardwire Zones and Zone Expansion

Hardwire Zones

HI LO

-zones V0-001

Normally Open Zones/ N.O. EOLR Zones

1.Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.

2.Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

Normally Closed Zones/ N.C. EOLR Zones

1.Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.

2.Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

End of Line Resistor (EOLR) Notes

If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.

Zone 1 is intended for EOLR only.

UL For UL commercial burglar alarm installations, use EOLR zones.

Double-Balanced Zones (V20P only)

Connect as shown below (resistor provided for one device).

IMPORTANT: Double-balanced zones provide zone tamper protection, and should be used as burglary zones only.

Do not use double-balanced zones as fire zones.

12

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TAMPER

2k CONTACTS 2k

2k TAMPER 2k

CONTACTS

2k

2k

ZONE 3

ZONE 4

zone-002-V0

Zone Doubling

(V20P only)

Smoke Detectors

TO ZONE 1

TERMINALS

2-WIRE

8

9

SMOKE

DETECTOR

-V0

HI

-001

LO

ZONE 1

5806

Fig. 7. Typical Double Balanced Zones

This feature provides two hardwired

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

normally closed zones for each standard

 

 

10

 

 

 

 

 

 

 

11

 

 

hardwired zone connected to the control’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals (but does not increase the total

 

 

 

ZONE 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of zones supported by the control). If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3k

 

 

 

 

 

enabled (Zone Programming mode,

 

 

 

ZONE 10

 

 

 

 

 

“Hardwire Type” prompt, option “3”),

 

 

 

 

 

 

V0

 

 

 

 

 

 

 

 

 

 

 

 

004-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hardwire zones are automatically paired as

 

 

 

 

 

 

 

 

6.2k

 

 

 

zone-

shown in the table. Connect as shown below

Fig. 8. Typical Zone Doubling Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(resistors provided).

 

 

 

 

 

 

 

Zone Doubling Table

 

 

 

 

 

Do not use zone doubling for fire

Zone

Paired with zone

 

 

 

 

 

zones.

2

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: A short across the EOL (i.e., at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal) on either zone of a zone-doubled

5

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pair or on a double-balanced zone causes a

6

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tamper condition (displayed as CHECK plus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

zone numbers).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the back this manual. Observe proper polarity when connecting the detectors.

2.Connect an EOL resistor across the loop wires at the last detector.

3.Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone from 2-8 as shown in Figure 7 (on next page).

Power Reset: This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.

NOTE: Maximum current on trigger 17 is 100mA.

2-6