Honeywell VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA Mounting and Wiring the Control, Zones

Models: VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA K5305-1V5

1 80
Download 80 pages 15.84 Kb
Page 13
Image 13
Smoke Detector Notes

 

 

Mounting and Wiring the Control

 

 

 

 

 

Smoke Detector Notes

Fire Verification (zone type 16): The control panel will “verify” a fire alarm by

 

 

resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds

 

 

for a second alarm trigger. If the smoke detector or thermostat does not trigger again,

 

 

the control will disregard the first trigger, and no alarm signal will occur. This feature

 

 

eliminates false alarms due to electrical or physical transients.

 

 

SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm

 

 

Listed relay accessories must be used to reset power as described in the Power Reset

 

 

paragraph above.

The zone 1 alarm current supports only one smoke detector in the alarmed state.

Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean-me option.

Do not use 4-wire smoke detectors on zone 1.

+

5

 

 

 

 

 

 

 

RELAY

 

 

 

 

AUX PWR

PROGRAM

BLK

 

+

RED

RELAY

 

 

 

 

 

OUTPUT

AS ZONE

 

 

 

 

EOL

TERMINALS

TYPE 54

 

 

 

 

 

 

 

 

POWER

 

(FIRE ZONE

 

 

 

N.O.

SUPERVISION

 

RESET)

 

 

 

 

 

 

 

 

RELAY MODULE

 

4

 

 

 

 

 

N.C.

 

 

 

A77-716B.

 

 

 

 

 

CONTACT OPENS

 

 

 

 

USE N.O.

 

 

 

 

CONTACT,

MOMENTARILY UPON

+

 

 

 

 

VIOLET

WHICH CLOSES

FIRE ALARM RESET

 

 

 

 

 

4-WIRE SMOKE

 

 

 

WHEN POWER

 

 

 

 

 

IS APPLIED.

 

 

OR COMBUSTION

 

 

 

 

 

DETECTOR

2000

 

 

 

 

 

 

 

 

 

 

 

OHMS

 

 

 

 

 

EOLR

 

 

 

TO ZONE TERM. (+)

 

 

 

 

-V0

 

 

 

 

-007

 

 

HEAT

 

 

 

 

 

 

 

 

wiresmk

 

DETECTOR

 

 

 

TO ZONE TERM. ( )

 

 

 

 

 

 

 

 

 

 

4

Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset

AUX PWR (+) 5

_

BLK

_

+

RED

TO OUTPUT 17 ( )

 

PROGRAM OUTPUT 17

 

 

 

 

EOL

FOR "OUT NORM

 

 

 

 

POWER

LOW" = YES IN

79 MENU

+

 

 

N.O.

SUPERVISION

MODE AND AS ZONE

 

 

RELAY MODULE

 

 

 

VIOLET

TYPE 54 IN

4-WIRE SMOKE

 

 

A77-716B.

80 MENU MODE

OR COMBUSTION

 

 

 

USE N.O.

 

 

DETECTOR

2000

 

 

CONTACT,

 

 

 

 

 

 

 

 

OHMS

 

 

WHICH CLOSES

 

 

 

EOLR

 

 

WHEN POWER

 

 

 

 

 

 

IS APPLIED.

TO ZONE TERM. (+)

 

 

 

 

4 wiresmk-008V0-

 

 

HEAT

 

 

 

TO ZONE TERM. ( )

DETECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset

4219/4229 Expansion

1. Connect each module to the control’s keypad terminals and set the device addresses.

Zones

VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.

VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules.

2.Connect sensors to the module’s loops. See Figure 8 on the following page.

• Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229 modules. (EOLRs used on the control terminals are 2000 ohms.)

Expansion zones have normal response time (300–500 msec), except zone connected to each module’s loop “A,” which can be set for fast response (10–15 msec).

3.If using relays with the 4229, connect the desired field wiring to the unit's relay contact terminals.

2-7