Honeywell K5305-1V5 Menu Mode: Defining Output Functions, Installation and Setup Guide, Prompt

Models: VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA K5305-1V5

1 80
Download 80 pages 15.84 Kb
Page 46
Image 46
*80 Menu Mode: Defining Output Functions

Installation and Setup Guide

*80 Menu Mode: Defining Output Functions

Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components:

Output Definition Components

Component

Description

Output Function No.

A reference number that defines an output’s characteristics.

Activated By

Determines whether the initiating event occurs on a zone, a zone list, or a zone type.

Event

Event that triggers the output action. Can be an event occurring on a specific zone number or

 

a zone list, or a specific zone type.

Partition

If the output is activated by zone type, this defines the partition in which the programmed

 

event is to cause the device action.

Output Action

Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2

 

seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.),

 

toggle the device state, or activate for a defined duration (set in data field *177).

Output No.

Assigns this function to a specific output number (defined in *79 Menu Mode). This is the

 

output number that will perform this function upon the triggering event. Note that each

 

defined function is associated with only one output number. This means that if more than one

 

output device needs to perform this particular function, you need to define another output

 

function number with the same attributes, but assign the appropriate output number. (i.e.

 

output devices can be assigned more than one function number, but each function number can

 

only be assigned a single output number.

For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:

Prompt

 

Entry

Output Funct. #

=

01

(assuming this is the first output function)

Activated By:

=

3 (zone number)

Enter Zn No.

=

04

(requires 2-digit zone numbers)

Output Action

=

3 (continuous pulse)

Output Number

=

02

(device mapped in *79 Menu Mode)

Start Output Definition mode by pressing 80 while in Data Programming mode.

80 Menu Mode

 

 

 

Output Function No.

 

Output Funct. #

 

 

 

VISTA-20P: 01-48 = output function number; VISTA-15P: 01-24 = output function number

 

(00 = Quit)

01

 

[] to continue; 00 to quit

 

 

 

Enter the output function number to be defined (or 00 to exit).

 

 

 

 

 

 

 

Summary Screen

 

01 A

E

P Trig

 

[] to continue

 

?00 0

0

– ZL=00

 

This screen displays a summary of the current output programming (for this example, Zone

 

 

 

 

 

 

 

 

List has been selected-this is the default screen).

 

 

 

 

A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type

 

 

 

 

NOTE: A question mark in the summary screen indicates that the device number shown

 

 

 

 

has not been mapped. Use *79 Menu mode to map the device.

 

Activated By

01 Activated By:

0

= delete

Zone List

1 = zone list (go to “A” prompt)

 

2

= zone type (go to “B” prompt)

 

3

= zone number (go to “C” prompt;)

[] to continue

Select where the initiating event for this output definition is to occur as follows:

If you enter “0,” the following prompt appears:

Delete?

0 = NO, 1 = YES

Press 1 to delete this output definition. The system

deletes the output function and any previous programming.

5-10
Page 46
Image 46
Honeywell K5305-1V5 Menu Mode: Defining Output Functions, Installation and Setup Guide, Output Definition Components, 5-10