Honeywell VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA Menu Mode Programming, Output Action

Models: VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA K5305-1V5

1 80
Download 80 pages 15.84 Kb
Page 47
Image 47
CHOICES FOR ZONE TYPES:

Menu Mode Programming

A

01 Zn List

1

Zone List (prompt appears if zone list was selected)

01-08 = zone list; [] to continue

Enter the desired zone list number associated with this output number. NOTE: Do not use pager zone lists 09-12 in output definitions.

Enter the zone list event that will activate this output.

Enter Event

 

0

= restore; 1 = alarm;

Alarm

1

2

= fault; 3= trouble

 

 

 

 

 

 

 

 

NOTE: For alarm, fault, and trouble, an event on ANY zone in the list activates the output, but ALL zones in the list must be restored before the output is restored.

Press [] to continue and skip to the “Output Action” prompt.

B

01 Enter Zn type

Perimeter 03

C

01 Enter Zn No.

12

Zone Type (prompt appears if zone type was selected)

Enter the desired zone type associated with this output number. See below for a list of available zone types.

CHOICES FOR ZONE TYPES:

00

= Not Used

05

= Day/Night

12

= Monitor Zone

01

= Ent/Exit #1

06

= 24 Hr Silent

14

= Carbon Monoxide

02

= Ent/Exit #2

07

= 24 Hr Audible

16

= Fire w/verification

03

= Perimeter

08

= 24 Hr Aux

23

= No Alarm Response

04

= Interior Follower

09

= Fire

24

= Silent Burglary

 

 

10

= Interior w/Delay

77

= Keyswitch Zone

 

 

 

 

 

81

= AAV Monitor Zone

 

 

 

 

 

90-91 = Configurable

CHOICES FOR SYSTEM OPERATION:

 

20

= Arming–Stay

36

= **At Bell Timeout***

52

= Kissoff

21

= Arming–Away

38

= Chime

 

54

= Fire Zone Reset

22

= Disarming

39

= Any Fire Alarm

 

58

= Duress

31

= End of Exit Time

40

= Bypassing

 

60

= AAV

32

= Start of Entry Time

41

= **AC Power Failure

66

= Function Key†

33

= Any Burglary Alarm 42 = **System Battery Low 67 = Bell Fail

 

 

43

= Comm. Failure

 

68

= Telco Line Cut

 

 

 

 

 

 

78

= Keyswitch Red LED

 

 

 

 

 

 

79

= Keyswitch Green LED

**Use 0 (Any) for Partition No. (P) entry.

***Or at Disarming, whichever occurs earlier.

Use *57 Menu Mode to assign the function key (function “07”).

Note: In normal operation mode:

Code + # + 7 + NN Key Entry starts Device NN.

Code + # + 8 + NN Key Entry stops Device NN.

Enter the partition in which this zone type will occur.

01 Partition

 

0 = any partition; 1 = partition 1;

Any partition

0

2 = partition 2; 3 = common

 

 

 

Press [] to continue and skip to the “Output Action” prompt.

Zone Number (prompt appears if zone number was selected) Enter the desired zone number associated with this output number. Press [] to continue.

Enter the zone event that will activate this output.

01 Enter Event

Restore0

0 = restore; 1 = alarm/fault/trouble

Press [] to continue to the “Output Action” prompt

01 Output Action

 

Close for 2 sec

1

Output Action

0

= off

4

= Change Device State

1

= Close for 2 seconds

5

= Duration 1 (see data field *177)

2

= Stay Closed

6

= Duration 2 (see data field *177)

3 = Pulse on & off (1 sec ON, 1 sec OFF)

Enter the desired device action as listed above. Press the [] key to continue.

5-11

Page 47
Image 47
Honeywell VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA, K5305-1V5 setup guide Menu Mode Programming, Output Action, 5-11