Honeywell VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA Menu Mode Programming, Output Type

Models: VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA K5305-1V5

1 80
Download 80 pages 15.84 Kb
Page 45
Image 45
Device Output Number

Menu Mode Programming

Start Output Device Mapping by pressing *79 while in Data Programming Mode. ∗79 Menu Mode

 

 

 

Device Output Number

 

ENTER OUTPUT NO.

 

01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10

 

00 = QUIT

xx

 

[] to continue; 00 to quit

 

 

 

 

 

 

 

 

 

This is the logical (or reference) relay number as used in the system. Relays and X-10

 

 

 

devices are numbered 01-16; the on-board triggers are numbered 17 and 18 and can be

 

 

 

programmed for inverted output, if required. Use the worksheet on the Programming Form

 

 

 

(printed separately) to organize device numbers.

17 OUT NORM LOW

 

0 = NO 1 = YES

0

Output Normally Low (prompt appears only for Triggers 17 and 18)

0 = no (standard default); 1 = yes [] to continue

Selecting 0 (no) sets the output level normally high (default setting). Selecting 1 (yes) sets the output normally low.

Output Trigger 17 can be used for resetting 4-wire smoke detectors by connecting it to the negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as zone type 54, fire zone reset, in *80 Menu mode.

After entry, display returns to Output Number prompt. Use *80 Menu mode to program the function of the trigger.

XXOUTPUT TYPE

DELETE0

Output Type

0 = delete; 1 = relay on 4204/4229 module; 2 = Powerline Carrier device (X-10) [] to continue

Select whether this is a relay or a Powerline Carrier (X-10) device. If Powerline Carrier is selected, go to “A” prompt.

If relay is selected, skip to “B” prompt.

“A”

XX UNIT No.

yy

Unit Number (prompt appears if X-10 is selected) 01-16 = predefined address

[] to continue

Enter the unit code (set at the device) and press [∗]. The system returns to the Output Number prompt.

“B”

XXMODULE ADDR

07-15yy

Module Address (prompt appears if relay is selected)

07-15 = predefined address [] to continue

Enter the predefined address for this module as listed below. Make sure the module’s DIP switches are set to the selected address.

Module Addresses

 

Address

Module

† These addresses apply to VISTA-20P only.

 

07

1st 4229 (with zones 09-16)

 

 

08

2nd 4229 (with zones 17-24)

 

 

09

3rd 4229 (with zones 25-32)

 

 

10

4th 4229 (with zones 33-40)

 

 

11

5th 4229 (with zones 41-48)

 

 

12

1st 4204

 

 

13

2nd 4204

 

 

14

3rd 4204

 

 

15

4th 4204

 

 

 

 

 

XX REL POSITION

1-4zz

Relay Position

1-4 = relay position [] to continue

This is the actual (or physical) relay number with respect to the Relay Module upon which it is located. For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers are 1-2.

The system returns to the Output Number prompt for programming the next device.

5-9

Page 45
Image 45
Honeywell VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA Menu Mode Programming, Device Output Number, Output Type