IBM 9179-MHB, 9117-MMB manual Did the Resource Repair Action menu appear? No Go to step

Models: 9117-MMB 9179-MHB

1 120
Download 120 pages 7.28 Kb
Page 84
Image 84

b.Select Commit.

c.Follow any instructions that are shown.

d.If a Do you want to review the previously displayed error? message is shown, select Yes and press Enter.

e.If an SRN is shown, suspect a loose card or connection. If no obvious problem is shown, record the SRN and contact your service provider for assistance..

f.If no SRN is shown, go to 5.

5.Test the part by doing the following:

a.At the command line, type diagmenu and press Enter.

b.From the Function Selection menu, select Advanced Diagnostics Routines and press Enter.

c.From the Diagnostic Mode Selection menu, select System Verification and press Enter.

d.Select All Resources, or select the diagnostics for the individual part to test only the part you replaced, and any devices that are attached to the part you replaced and press Enter.

Did the Resource Repair Action menu appear? No: Go to step 6.

Yes: Go to step 7.

6.Did the Testing Complete, No trouble was found message appear?

v No: There is still a problem. Contact your service provider. This ends the procedure.

v Yes: Select Log Repair Action, if not previously logged, from the Task Selection menu to update the AIX error log. If the repair action was reseating a cable or adapter, select the resource associated with that repair action. If the resource associated with your action is not displayed on the Resource List, select sysplanar0 and press Enter.

Tip: This action changes the indicator light for the part from the fault state to the normal state. Go to step 9 on page 73

7.Select the resource for the replaced part from the Resource Repair Action menu. When a test is run on a resource in system verification mode, and that resource has an entry in the AIX error log, if the test on the resource was successful, the Resource Repair Action menu appears. Complete the following steps to update the AIX error log to indicate that a system-detectable part has been replaced.

Note: On systems with a indicator light for the failing part, this changes the indicator light to the normal state.

a.Select the resource that has been replaced from the Resource Repair Action menu. If the repair action was reseating a cable or adapter, select the resource associated with that repair action. If the resource associated with your action does not appear on the Resource List, select sysplanar0. Press Enter.

b.Select Commit after you make your selections. Did another Resource Repair Action display appear?

No: If the No Trouble Found display appears, go to step 9 on page 73

Yes: Go to step 8.

8.Select the parent or child of the resource for the replaced part from the Resource Repair Action menu if necessary. When a test is run on a resource in system verification mode, and that resource has an entry in the AIX error log, if the test on the resource was successful, the Resource Repair Action menu appears. Complete the following steps to update the AIX error log to indicate that a system-detectable part has been replaced.

Note: This changes the indicator light for the part from the fault state to the normal state.

72Power Systems: Power supplies for the 9117-MMB or 9179-MHB

Page 84
Image 84
IBM 9179-MHB, 9117-MMB manual Did the Resource Repair Action menu appear? No Go to step