Light Path Diagnostics table
The
Table 3. Light Path Diagnostics
Lit LED | Cause | Action |
|
|
|
BladeCenter system LED panel |
| |
|
|
|
Location | A condition has occurred in this BladeCenter | Look for any information or error LEDs on the |
| unit that has caused the remote system | |
| management to identify this BladeCenter unit | blades in the this BladeCenter unit, and follow |
| as needing attention. | the instructions in this table for those LEDs. |
|
|
|
The system temperature has exceeded a | 1. Check to see if a blower module has failed. | |
| threshold level. | |
| If it has, replace the blower module as | |
|
| |
|
| soon as possible to regain redundancy. |
|
| 2. Make sure the room temperature is not too |
|
| high. (See “Features and specifications” on |
|
| page 5 for temperature information.) |
|
| 3. Check to see if a blade server has a |
|
| temperature LED lit. If it has, see the |
|
| documentation that comes with the blade |
|
| server. |
|
| 4. Make sure there is a blade, module, or filler |
|
| plugged in each bay. |
|
| If the problem remains, have the system |
|
| serviced. |
|
|
|
Information | A noncritical event has occurred that should be | Check the error log for the messages. Check |
| looked at, such as the wrong I/O module | the LEDs on the BladeCenter unit and the |
| inserted in a bay, or power needs that exceed | blade servers to isolate the component. |
| the capacity of power modules currently |
|
| installed. |
|
|
|
|
System error | A critical system error has occurred, such as | 1. Check the error log for messages. |
| ||
| 2. Look for an error LED on the modules and | |
| system error in a blade. | |
| blades to locate the component. | |
|
| |
|
| v If the error LED is on a module, follow |
|
| the instructions for the module in this |
|
| table. |
|
| v If the error LED is on a blade, see the |
|
| documentation that comes with the |
|
| blade. |
|
|
|
Management module |
| |
|
|
|
Management- | A critical error has occurred in the | Unplug the management module and reinsert |
module error | management module. | it, then, restart the BladeCenter unit. If the |
|
| problem remains, replace the management |
|
| module. |
|
|
|
Management- | After adding or restarting an Ethernet switch | You must wait until the Ethernet switch module |
module Web | module through the | completes POST. After Ethernet switch module |
interface to | interface, the Web page does not refresh. You | POST is complete, you will be able to connect |
Ethernet switch | will also be unable to connect to the Ethernet | to the Ethernet switch module. |
module does not | switch module through the Telnet interface. |
|
refresh |
|
|
|
|
|
Power module |
|
|
|
|
|
Chapter 6.