Touch Screen Display
User Settings
The User Settings choice allows you to adjust the
To access the User Settings dialog box:
1.Select CONFIG.
2.Select USER SETTINGS from the
The User Settings dialog box is displayed. See Figure 67. The top six buttons access a series of secondary dialog boxes to configure the various settings.
Figure 67 User settings dialog box
Source Setpoints
The Source 1/2 Setpoints allows you to configure trigger points for each input source (1 or 2) for the STS2/PDU via a keypad dialog or HI/LO dialog box. The source numbers do not designate the source as the preferred or alternate source. The numbers simply identify the input source. See 10.2 - Man- ual Transfer / Preferred Source Selection to set the preferred source.
The Setpoints are based on values in relation to the nominal voltage required for the STS2/PDU. UV refers to under voltage, meaning the amount of voltage below the nominal voltage. OV refers to over voltage or the amount of voltage over the nominal voltage.
•Fast UV Setting (%) — if the voltage drops below this set percentage of the nominal voltage, the STS2/PDU transfers from the current source to the opposite source.
•Slow UV Setting (%) — if the voltage remains this set percentage below the nominal voltage for the period of the slow detection delay, the STS2/PDU transfers from the current source to the opposite source.
•Slow UV detection delay — the number of cycles that the source must remain below the Slow UV Setting before the STS2/PDU transfers.
•OV Setting (%) — if the voltage exceeds this set percentage of the nominal voltage for the period of the OV detection delay, the STS2/PDU transfers from the current source to the opposite source.
•OV Detection Delay — the number of cycles that the source must remain above the OV Setting before the STS2/PDU transfers sources.
•
101