Location Considerations

2.4Altitude

The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200m).

Figure 1 Recommended derating for high altitude operation

Rating (%)

100

98

96

94

92

90

88

86

0

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

Operation at full load at a higher altitude can be accommodated in ambient temperatures less than 104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load operation at altitudes above 4000 feet (1200m).

Figure 2 Maximum ambient temperature for full load operation at higher altitudes

Ambient Temperature

°F (°C)

Max.

 

104.0(40)

102.2(39)

100.4(38)

98.6(37)

96.8(36)

95.0(35)

93.2(34)

94.1(33)

89.6(32)

87.8(31)

86.0 (30)

0

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

 

 

 

 

Altitude—Feet

 

 

 

 

 

Table 3 Altitude conversion—feet to meters

Feet = Meters

4000 = 1200

4500 = 1372

5000 = 1524

5500 = 1676

6000 = 1829

6500 = 1981

7000 = 2134

7500 = 2286

8000 = 2438

8500 = 2591

9000 = 2743

9500 = 2896

10000 = 3048

6

Page 14
Image 14