Touch Screen Display

PDU Setpoints

The PDU Setpoints option allows you to configure the following parameters for the PDU, shown in Figure 69.

Load Voltage THD (%)

Neutral Current (% of nom)

Ground Current (A)

Load Bus Overcurrent (% of nom)

Figure 69 PDU setpoints

Table 18 shows the range of valid values, default values and resolution for each parameter.

Table 18 PDU setpoints

Button

Range

Default

Resolution

 

 

 

 

Load Voltage THD (%)

3.0% to 99.9%

15.0%

0.1

 

 

 

 

Neutral Current (% of nom)

10% to 200%

95%

1

 

 

 

 

Ground Current (A)

1.0A to 50.0A

5.0A

0.1

 

 

 

 

Load Bus Overcurrent (% of nom)

50% to 100%

100%

 

 

 

 

System Settings

The System Settings choice under the Config menu displays another pop-up menu with three choices:

Comm Options

System Options

System ID

To access the System Settings menu:

1.Select CONFIG from the menu bar.

2.Select SYSTEM SETTINGS from the Config menu.