Specifications
14.2.1Frame and Enclosure
The complete STS2/PDU is housed in a freestanding enclosure. The cabinet is a NEMA type 1 enclo- sure. The cabinet is structurally designed to handle lifting from the base. The frame is designed to accommodate floor stands.
Table 25 Frame sizes
Rating | Width x Depth x Height | |
in. (mm) | ||
| ||
|
| |
250A | 60 x 32 x 77 (152 x 81 x 196)* | |
|
| |
400 – 600A | 73 x 49 x 77 (186 x 125 x 196) | |
|
| |
800A | 96 x 49 x 77 (244 x 125 x 196) | |
|
|
* Width is 76.8 in (195 cm) with output distribution cabinet
The distributed floor weight for STS2/PDU is less than 260 lbs./sq. ft. (118 kg/m²).
The required service access is front and one side of the unit, 250A without output cabinet is front access only. Side access depends on which side the output cabinet is mounted, can be left or right.
The STS2/PDU can be tipped 15° in any direction without falling over.
14.2.2Caster and Leveling - 250A only
The 250A unit frame includes
14.2.3Cooling
The STS2/PDU 250A units utilize convection air cooling for the enclosure with forced air cooling of the heat sinks.
The
Air intake is through screened protective openings in the front of the unit. A standard furnace filter is installed behind the openings.
By opening the front door, the filter can be changed easily without exposing personnel to high voltage. The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).
The air exhaust is through the top of the unit.
117