Communication Interfaces
Table 15 shows the various groups, the settings contained within and the type of value it requires.
Table 15 Group settings and values
Group | Item: | Description | Value Type | Value Notes | |
|
|
|
|
| |
| 1 | Input Volts (PDU) | Integer | Set per system spec. | |
Group 1: |
|
|
|
| |
2 | Volts | Integer | Set per system spec. | ||
System |
|
|
|
| |
3 | Current | Integer | Set per system spec. | ||
Ratings | |||||
| 4 | Frequency | Scaled | Desired freq. x 10 (600 = 60 Hz) | |
|
|
|
|
| |
| 1 | Language | Enumeration | [Not supported at this time] | |
|
|
|
|
| |
| 2 | System Model Number | String | 14 Character max. | |
|
|
|
|
| |
| 3 | System ID Number | String | 8 Character max. | |
|
|
|
|
| |
| 4 | System Tag Number | String | 8 Character max. | |
|
|
|
|
| |
| 5 | System Order Number | String | 8 Character max. | |
|
|
|
|
| |
| 6 | Options_1 | Bitpacked | 14 Character max. | |
|
|
|
|
| |
| 7 | Autodial Primary Line | String | 20 Character max. | |
Group 2: |
|
|
|
| |
8 | Autodial Secondary Line | String | 20 Character max. | ||
System |
|
|
|
| |
9 | Autodial Pager Number | String | 20 Character max. | ||
Settings | |||||
| 10 | Autodial Pager PIN | String | 10 Character max. | |
|
|
|
|
| |
| 11 | Modem Init String | String | 20 Character max. | |
|
|
|
|
| |
| 12 | Modem Baud Rate | Enumeration | 0 = 2400, 1 = 9600, & 2 = 19200 bps | |
|
|
|
|
| |
| 13 | Modem LGS Check - Day | Bitpacked |
| |
|
|
|
|
| |
| 14 | Modem LGS Check - Time | Bitpacked |
| |
|
|
|
|
| |
| 15 | Comms Options 1 | Bitpacked | See section 12.1.3. | |
|
|
|
|
| |
| 16 | Comms Options 2 | Bitpacked | See section 12.1.3. | |
|
|
|
|
| |
| 1 | SRC1 Fast Undervoltage Setpoint | Integer | In % of nominal below nominal | |
|
|
|
|
| |
| 2 | SRC1 Slow Undervoltage Setpoint | Integer | In % of nominal below nominal | |
|
|
|
|
| |
| 3 | SRC1 Slow Undervoltage Detect Delay | Integer | In number of lines cycles | |
|
|
|
|
| |
| 4 | SRC1 Overvoltage Setpoint | Integer | In % of nominal above nominal | |
|
|
|
|
| |
| 5 | SRC1 Overvoltage Detect Delay | Integer | In 1/4 lines cycles | |
|
|
|
|
| |
| 6 | SRC1 I peak Transfer Setpoint | Integer | x 10 | |
|
|
|
|
| |
| 7 | SRC2 Fast Undervoltage Setpoint | Integer | In % of nominal below nominal | |
|
|
|
|
| |
| 8 | SRC2 Slow Undervoltage Setpoint | Integer | In % of nominal below nominal | |
Group 3: |
|
|
|
| |
9 | SRC2 Slow Undervoltage Detect Delay | Integer | In number of lines cycles | ||
User |
|
|
|
| |
10 | SRC2 Overvoltage Setpoint | Integer | In % of nominal above nominal | ||
Settings | |||||
| 11 | SRC2 Overvoltage Detect Delay | Integer | In 1/4 lines cycles | |
|
|
|
|
| |
| 12 | SRC2 I peak Transfer Setpoint | Integer | x 10 | |
|
|
|
|
| |
| 13 | Max. Transfer Phase Angle | Integer | In degrees | |
|
|
|
|
| |
| 14 | Output Frequency Deviation | Integer | Freq. in Hz x 10 | |
|
|
|
|
| |
| 15 | ReTransfer Delay Time | Integer | In seconds | |
|
|
|
|
| |
| 16 | Horn Volume | Integer | Range: | |
|
|
|
|
| |
| 17 | Critical Option Enabling | Bitpacked | See section 12.1.3. | |
|
|
|
|
| |
| 18 | Bitpacked | See section 12.1.3. | ||
|
|
|
|
| |
Group 4: | 1 to 63 | Event Mask settings for faults | Event Mask | See section 12.1.3. | |
Event |
|
|
|
| |
|
|
|
| ||
Mask | 64 to 143 | Event Mask settings for alarms | Event Mask | See section 12.1.3. | |
Settings |
|
|
|
|