Alarms and Faults

Table 12 Event messages (continued)

 

 

 

 

 

ID

Alarm Message

Description/Cause

Action

 

 

 

 

81

SOURCES OUT OF SYNC

Source 1 and Source 2 are out of synchronization.

A, E

 

 

 

 

82

LOAD ON ALT SOURCE

The output load is running on the alternate source.

A, E

 

 

 

 

83

AUTO REXFER INHIBIT

Automatic retransfer is inhibited.

A, E

 

 

 

 

84

CB1 (S1) OPEN

Source 1, Circuit Breaker 1 is open.

A, E

 

 

 

 

85

CB2 (S2) OPEN

Source 2, Circuit Breaker 2 is open.

A, E

 

 

 

 

86

CB4 (S1 BYP) CLOSED

Source 1 on bypass, Circuit Breaker 4 is closed.

A, E

 

 

 

 

87

CB5 (S2 BYP) CLOSED

Source 2 on bypass, Circuit Breaker 5 is closed.

A, E

 

 

 

 

88

CB3 (OUTPUT) OPEN

Output circuit breaker (CB3) is open.

A, E

 

 

 

 

89

CB3A (OUTPUT) OPEN

Output circuit breaker (CB3A) is open.

A, E

 

 

 

 

90

S1 PHASE ROT ERROR

Source 1 phase rotation error.

A, E

 

 

 

 

91

S2 PHASE ROT ERROR

Source 2 phase rotation error.

A, E

 

 

 

 

92

TRANSFER INHIBITED

Transfer inhibited.

A, E

 

 

 

 

93

OUTPUT UV

Output is under voltage.

D, F, A, E

 

 

 

 

94

HISTORY LOG FULL

Both History Logs have been written and no more history logs can be

A, E

written without clearing one of the logs

 

 

 

96

INPUT 1 OV INPUT

Source 1 over voltage

A, E

 

 

 

 

97

INPUT 1 UV INPUT

Source 1 under voltage

A, E

 

 

 

 

98

INPUT 2 OV INPUT

Source 2 over voltage

A, E

 

 

 

 

99

INPUT 2 UV INPUT

Source 2 under voltage

A, E

 

 

 

 

100

LOAD OVERCURRENT

Output over current

A, E

 

 

 

 

101

GROUND OVERCURRENT

Ground over current

A, E

 

 

 

 

102

NEUTRAL OVERCURRENT

Neutral over curremt

A, E

 

 

 

 

103

LOAD VOLTAGE THD

Voltage THD has exceeded the set limit

A, E

 

 

 

 

104

INPUT 1 CB6 OPEN

Source 1 input Circuit Breaker 6 is open

A, E

 

 

 

 

105

INPUT 2 CB7 OPEN

Source 2 Input Circuit Breaker 7 is open

A, E

 

 

 

 

106

INPUT 1 OF/UF

Source 1 over frequency/under frequency

A, E

 

 

 

 

107

INPUT 2 OF/UF

Source 2 over frequency/under frequency

A, E

 

 

 

 

120

INPUT CONTACT #1

Input Contact # x is an optional alarm input. The alarm name can be

 

121

INPUT CONTACT #2

programmed with an alarm name from the Input Contactor Isolator

 

122

INPUT CONTACT #3

settings option under the Comm Options. See Configuring the Input

 

123

INPUT CONTACT #4

Contact Isolator Settings on page 108. The alarm is sent to Monitor

A, E

124

INPUT CONTACT #5

DSP. The LCD logs the alarm with the programmed name. Monitor

 

125

INPUT CONTACT #6

DSP logs it with the generic name which is how it is reported to the

 

126

INPUT CONTACT #7

SVT query.

 

127

INPUT CONTACT #8

 

 

128

CONFIG MODIFIED

A setpoint configuration has changed.

E

 

 

 

 

129

PASSWORD CHANGED

The password for touch screen access has been modified and saved.

E

 

 

 

 

130

TIME REPROGRAMMED

The system’s time has been reset and saved.

E

 

 

 

 

131

DATE REPROGRAMMED

The system’s date has been reset and saved.

E

 

 

 

 

132

EVENT LOG CLEARED

The event log has been erased.

E

 

 

 

 

133

HIST LOGS CLEARED

Both History Logs have been erased.

E

 

 

 

 

134

XFER COUNT CLEARED

Transfer counter reset to 0

E

 

 

 

 

135

KWH COUNT CLEARED

KW-Hrs counter reset to 0

E

 

 

 

 