| Alarms and Faults | ||
Table 12 Event messages (continued) |
| |||
|
|
|
| |
ID | Alarm Message | Description/Cause | Action | |
|
|
|
| |
81 | SOURCES OUT OF SYNC | Source 1 and Source 2 are out of synchronization. | A, E | |
|
|
|
| |
82 | LOAD ON ALT SOURCE | The output load is running on the alternate source. | A, E | |
|
|
|
| |
83 | AUTO REXFER INHIBIT | Automatic retransfer is inhibited. | A, E | |
|
|
|
| |
84 | CB1 (S1) OPEN | Source 1, Circuit Breaker 1 is open. | A, E | |
|
|
|
| |
85 | CB2 (S2) OPEN | Source 2, Circuit Breaker 2 is open. | A, E | |
|
|
|
| |
86 | CB4 (S1 BYP) CLOSED | Source 1 on bypass, Circuit Breaker 4 is closed. | A, E | |
|
|
|
| |
87 | CB5 (S2 BYP) CLOSED | Source 2 on bypass, Circuit Breaker 5 is closed. | A, E | |
|
|
|
| |
88 | CB3 (OUTPUT) OPEN | Output circuit breaker (CB3) is open. | A, E | |
|
|
|
| |
89 | CB3A (OUTPUT) OPEN | Output circuit breaker (CB3A) is open. | A, E | |
|
|
|
| |
90 | S1 PHASE ROT ERROR | Source 1 phase rotation error. | A, E | |
|
|
|
| |
91 | S2 PHASE ROT ERROR | Source 2 phase rotation error. | A, E | |
|
|
|
| |
92 | TRANSFER INHIBITED | Transfer inhibited. | A, E | |
|
|
|
| |
93 | OUTPUT UV | Output is under voltage. | D, F, A, E | |
|
|
|
| |
94 | HISTORY LOG FULL | Both History Logs have been written and no more history logs can be | A, E | |
written without clearing one of the logs | ||||
|
|
| ||
96 | INPUT 1 OV INPUT | Source 1 over voltage | A, E | |
|
|
|
| |
97 | INPUT 1 UV INPUT | Source 1 under voltage | A, E | |
|
|
|
| |
98 | INPUT 2 OV INPUT | Source 2 over voltage | A, E | |
|
|
|
| |
99 | INPUT 2 UV INPUT | Source 2 under voltage | A, E | |
|
|
|
| |
100 | LOAD OVERCURRENT | Output over current | A, E | |
|
|
|
| |
101 | GROUND OVERCURRENT | Ground over current | A, E | |
|
|
|
| |
102 | NEUTRAL OVERCURRENT | Neutral over curremt | A, E | |
|
|
|
| |
103 | LOAD VOLTAGE THD | Voltage THD has exceeded the set limit | A, E | |
|
|
|
| |
104 | INPUT 1 CB6 OPEN | Source 1 input Circuit Breaker 6 is open | A, E | |
|
|
|
| |
105 | INPUT 2 CB7 OPEN | Source 2 Input Circuit Breaker 7 is open | A, E | |
|
|
|
| |
106 | INPUT 1 OF/UF | Source 1 over frequency/under frequency | A, E | |
|
|
|
| |
107 | INPUT 2 OF/UF | Source 2 over frequency/under frequency | A, E | |
|
|
|
| |
120 | INPUT CONTACT #1 | Input Contact # x is an optional alarm input. The alarm name can be |
| |
121 | INPUT CONTACT #2 | programmed with an alarm name from the Input Contactor Isolator |
| |
122 | INPUT CONTACT #3 | settings option under the Comm Options. See Configuring the Input |
| |
123 | INPUT CONTACT #4 | Contact Isolator Settings on page 108. The alarm is sent to Monitor | A, E | |
124 | INPUT CONTACT #5 | DSP. The LCD logs the alarm with the programmed name. Monitor | ||
| ||||
125 | INPUT CONTACT #6 | DSP logs it with the generic name which is how it is reported to the |
| |
126 | INPUT CONTACT #7 | SVT query. |
| |
127 | INPUT CONTACT #8 |
|
| |
128 | CONFIG MODIFIED | A setpoint configuration has changed. | E | |
|
|
|
| |
129 | PASSWORD CHANGED | The password for touch screen access has been modified and saved. | E | |
|
|
|
| |
130 | TIME REPROGRAMMED | The system’s time has been reset and saved. | E | |
|
|
|
| |
131 | DATE REPROGRAMMED | The system’s date has been reset and saved. | E | |
|
|
|
| |
132 | EVENT LOG CLEARED | The event log has been erased. | E | |
|
|
|
| |
133 | HIST LOGS CLEARED | Both History Logs have been erased. | E | |
|
|
|
| |
134 | XFER COUNT CLEARED | Transfer counter reset to 0 | E | |
|
|
|
| |
135 | KWH COUNT CLEARED | E | ||
|
|
|
|