Output Power Wiring
5.0OUTPUT POWER WIRING
The STS2/PDU standard model is provided with a circuit breaker for connecting to the load or a remote distribution cabinet. Other distribution configurations are available.
The three main types of distributions available for the STS2/PDU are:
•Output Breaker
•Inline
•Square D
For other optional distribution methods, contact your local Liebert representative or call
The STS2/PDU distribution may be mounted on either the right or left side at the customer’s option. Location of output conduit connections is affected by the location of the output cabinet. See Figures 8, 9, 12, 13, 16 and 17 for wiring a
Figures 10, 11, 14, 15, 18 and 19 for wiring a left-side distribution configuration. See Figures 23 through 44 for wiring.
See Table 7 for wiring the various output options.
5.1Customer Connections
The customer is responsible for connections from the STS2/PDU distribution to the connected load, either directly or through remote distribution cabinets.
Table 7 | Distribution configurations | ||
|
|
|
|
|
| For Details See |
|
Distribution Type | Electrical Output |
| |
Field Connections |
| ||
Output Breaker |
|
| |
|
|
|
|
| 250A | Figure 23 |
|
|
|
|
|
| Figure 33 |
| |
|
|
|
|
| 800A | Figure 35 |
|
|
|
| |
Inline Panelboards |
|
| |
|
|
|
|
| 250A | Figure 30 |
|
|
|
|
|
| Figure 31 |
| |
|
|
| |
Figure 32 |
| ||
|
|
|
|
13