Liebert PDUTM, STS2 manual To configure the setpoints for each source, Setpoint parameters

Models: STS2 PDUTM

1 156
Download 156 pages 3.28 Kb
Page 110
Image 110

Touch Screen Display

To configure the setpoints for each source:

1.Select SOURCE 1/2 SETPOINTS from the User Settings dialog box. The Source 1/2 Setpoints dialog is displayed.

Figure 68 Source setpoints

2.Select 1 to configure the settings for Source 1.

3.Configure the settings using the keypad or dialog box that is displayed when you touch a button.

Table 17 Setpoint parameters

Button

Range

Default

Comments

Fast UV Setting (%)

-10 to -30% of Nominal

-20%

Set in increments of 1%.

voltage rating

 

 

 

Slow UV Setting (%)

-5 to -20%

-10%

Set in increments of 1%.

 

 

 

 

Slow UV detection delay

1-60 cycles

5 cycles

Units: Line Cycle

 

 

 

 

OV Setting (%)

+5% to +20%

+10%

Set in increments of 1%.

 

 

 

 

OV Detection Delay

1-255 cycles

3 cycles

Units: 1/4 Line Cycle

 

 

 

 

 

0 – 3.0 multiplied by

2.5 Times Unit

I-peak xfer lockout detection point.

I-PK Xfer Lockout

Units: Amps RMS. Select the HI or

the unit current rating.

Current Rating

 

LO buttons to configure your setting.

 

 

 

 

 

 

 

4.Select 2 for Source 2.

5.Configure the settings, as described in step 3.

6.Select SAVE to keep the settings for both sources. The Setpoints dialog is closed and the User Settings dialog is displayed.

7.Select MANUAL MAX XFER PHASE ANGLE. A keypad is displayed.

This setting configures the maximum allowed phase difference between the sources and applies to all manual transfers as well as any auto retransfer.

a.Configure this setting with a range of +/- 1-30 degrees. The default setting is +/-15 degrees and the resolution is 1 deg.

b.Select OK to save the setting. The setting is now displayed in the adjacent field in the User Settings dialog box.