Alarms and Faults

Table 12

 

Event messages

 

 

 

 

 

 

 

 

 

 

ID

 

 

Alarm Message

Description/Cause

 

Action

 

 

 

 

 

 

 

1

 

S1

SCR SHORT

One or more of the SCRs for Source 1 have shorted and failed.

 

D, F, A, E

 

 

 

 

 

 

 

2

 

S2

SCR SHORT

One or more of the SCRs for Source 2 have shorted and failed.

 

D, F, A, E

 

 

 

 

 

 

 

3

 

S1

SCR OPEN

One or more of the SCRs for Source 1 is open.

 

D, F, A, E

 

 

 

 

 

 

 

4

 

S2

SCR OPEN

One or more of the SCRs for Source 2 is open.

 

D, F, A, E

 

 

 

 

 

 

5

 

PRIMARY FAN FAIL

A primary cooling fan has failed and the unit is now being cooled by a

D, A, E

 

secondary fan, which is not monitored.

 

 

 

 

 

 

 

6

 

CONTROL MODULE FAIL

Control logic module has failed.

 

D, A, E

 

 

 

 

 

 

7

 

PWR SPLY DC A FAIL

Power supply DC bus A has failed.

 

D, A, E

 

 

 

 

 

 

8

 

PWR SPLY DC B FAIL

Power supply DC bus B has failed.

 

D, A, E

 

 

 

 

 

 

9

 

PWR SPLY S1 AC FAIL

Power supply Source 1 AC has failed.

 

D, A, E

 

 

 

 

 

 

10

 

PWR SPLY S2 AC FAIL

Power supply Source 2 AC has failed.

 

D, A, E

 

 

 

 

 

 

11

 

PWR SPLY LOGIC FAIL

A power supply module has failed.

 

D, A, E

 

 

 

 

 

 

12

 

OUT VOLT SENSE FAIL

The output volt sense module failed

 

D, A, E

 

 

 

 

 

 

 

13

 

S1

VOLT SENSE FAIL

The Source 1 volt sense module failed.

 

D, A, E

 

 

 

 

 

 

 

14

 

S2

VOLT SENSE FAIL

The Source 2 volt sense module failed.

 

D, A, E

 

 

 

 

 

 

 

15

 

S1

SCR SENSE FAIL

The Source 1 SCR sense module failed.

 

D, A, E

 

 

 

 

 

 

 

16

 

S2

SCR SENSE FAIL

The Source 2 SCR sense module failed.

 

D, A, E

 

 

 

 

 

 

 

17

 

S1

CURR SENSE FAIL

The Source 1 SCR current module failed.

 

D, A, E

 

 

 

 

 

 

 

18

 

S2

CURR SENSE FAIL

The Source 2 SCR current module failed.

 

D, A, E

 

 

 

 

 

 

 

19

 

S1

GATE DRIVE FAIL

The Source 1 gate drive module failed.

 

D, A, E

 

 

 

 

 

 

 

20

 

S2

GATE DRIVE FAIL

The Source 2 gate drive module failed.

 

D, A, E

 

 

 

 

 

 

21

 

INTERNAL COMM FAIL

Internal CAN communications failed.

 

D, A, E

 

 

 

 

 

 

23

 

CB1 SHUNT TRIP FAIL

CB1 shunt trip failed.

 

D, A, E

 

 

 

 

 

 

24

 

CB2 SHUNT TRIP FAIL

CB2 shunt trip failed.

 

D, A, E

 

 

 

 

 

 

27

 

EQUIPMENT FAN FAIL

One of the equipment fans failed

 

D, A, E

 

 

 

 

 

 

28

 

INPUT 1 SURGE FAIL

Source 1 input surge suppression module failed

 

D, A, E

 

 

 

 

 

 

29

 

INPUT 2 SURGE FAIL

Source 2 input surge suppression module failed

 

D, A, E

 

 

 

 

 

 

64

 

HEATSINK OVERTEMP

Heatsink has exceeded the recommended temperature.

 

A, E

 

 

 

 

 

 

65

 

EQUIPMENT OVERTEMP

Cabinet has exceeded the recommended temperature

 

A, E

 

 

 

 

 

 

 

67

 

S1

UV

Source 1 under voltage, fast detection.

 

A, E

 

 

 

 

 

 

 

68

 

S1

UV (RMS)

Source 1 under voltage, slow detection.

 

A, E

 

 

 

 

 

 

 

69

 

S1

OV

Source 1 over voltage

 

A, E

 

 

 

 

 

 

 

70

 

S1

OF/UF

Source 1 over frequency/under frequency

 

A, E

 

 

 

 

 

 

 

71

 

S1

FAIL

Source 1 failure.

 

A, E

 

 

 

 

 

 

 

72

 

S2

UV

Source 2 under voltage, fast detection.

 

A, E

 

 

 

 

 

 

 

73

 

S2

UV (RMS)

Source 2 under voltage, slow detection.

 

A, E

 

 

 

 

 

 

 

74

 

S2

OV

Source 2 over voltage.

 

A, E

 

 

 

 

 

 

 

75

 

S2

OF/UF

Source 2 over frequency/under frequency.

 

A, E

 

 

 

 

 

 

 

76

 

S2

FAIL

Source 2 failure.

 

A, E

 

 

 

 

 

 

 

77

 

S1

OVERCURRENT

Source 1 over current.

 

A, E

 

 

 

 

 

 

 

78

 

S2

OVERCURRENT

Source 2 over current.

 

A, E

 

 

 

 

 

 

 

79

 

S1

I-PEAK

I-PK on Source 1.

 

D, F, A, E

 

 

 

 

 

 

 

80

 

S2

I-PEAK

I-PK on Source 2.

 

D, F, A, E

 

 

 

 

 

 

 

85

Page 93
Image 93
Liebert STS2, PDUTM manual Event messages, Alarm Message Description/Cause Action