Specifications

14.2.11 RS-232 Interface Parameters

The service terminal interface parameters are the following settings and cannot be changed.

Table 28 RS-232 settings

Parameter

Setting

 

 

Interface

RS-232 Using EIA Voltage Levels

 

 

Baud Rate

9600

 

 

Parity

None

 

 

Number of Data Bits

8

 

 

Number of Stop Bits

1

 

 

Hardware Flow Control

Off

 

 

Terminator

<CR> <LF>

 

 

Handshaking

Not supported

 

 

Structure

Full duplex

 

 

Local Echo

Off

 

 

14.2.12 Maintenance Bypass

The STS2/PDU is configured to allow the unit’s electronics to be bypassed to either input source for maintenance without interruption of power to the load.

The STS2/PDU is furnished with key-interlocked maintenance bypass breakers to configure the bypass.

STS2/PDU units have all electronics isolated from the input, output and bypass connections to allow safe servicing of any components without access to hazardous voltages when the unit is in mainte- nance bypass.

See 10.4 - Maintenance Bypass for instructions.

14.2.13 Fuseless Design

All STS2/PDU units are fuseless.

14.2.14 Options

The following options are available for the STS2/PDU:

Panelboards

Subfeed Breakers

K-Factor Transformers

Surge Suppression System (TVSS)

Redundant Static Switch Output Breaker

Programmable Relay Board

Comms Board w/SiteScan and Modem Interface

Internal Modem

Input Contact Isolator Board

Network Interface Card (NIC)

Remote Source Selection

Key Lockout Switch

Export Crating

See 6.0 - Options for more information.