Operating Instructions
10.0OPERATING INSTRUCTIONS
! CAUTION
Before unit is placed into service for the first time, after equipment relocation or after the equipment has been
After the initial equipment
All programmable functions are preset at the factory to enable the unit to be brought up without the need to enter all selectable parameters.
The LCD touch screen is discussed in more detail in 13.0 - Touch Screen Display. See Figures 23 through 36 for circuit breaker locations.
10.1Normal System Turn-On
1.Depending on the type of distribution used:
•If equipped with output breaker CB8, open CB8.
•If equipped with output inline panelboards, open panelboard main breakers CB8 and CB9 and, if supplied, CB10 and CB11.
•If optional subfeed breakers are supplied, open subfeed breakers CB12 and CB13.
See Figures 3 through 6 for location of breakers.
a.Retract the bolts on the key interlocks for CB1 and CB2.
b.Extend the bolts on the key interlocks for CB4 and CB5, thus preventing CB4 or CB5 from being turned ON.
2.Apply source/input power to both STS2/PDU inputs by closing CB6 and CB7.
The touch screen control panel should become active and operate properly when at least one of the inputs is energized.
3.Verify that nominal input voltages are applied to both inputs (Source 1 and Source 2).
The input voltages, selected preferred source, breaker and switch status and alarms are indicated on the Mimic screen.
Figure 59 STS2/PDU touch screen display
Mimic
Sources
Event controls
Static
Transfer
Switch
Event display