14.0SPECIFICATIONS

14.1System Configuration

The STS2/PDU can be set in several different configurations, according to the model and location. The configuration is set at the factory and does not need to be changed by the customer.

14.1.1Frequency

The STS2/PDU accepts input frequencies of 50 Hz or 60 Hz, depending on the model ordered. The fre- quency shall be within +/- 0.5 Hz of the nominal frequency.

14.1.2Input Voltage

The STS2/PDU models are available to handle various voltages. The input voltage must be three phase AC (3 wire-plus-ground). The voltage shall be within +/- 10% of the nominal voltage.

The following table provides nominal voltages, listed according to frequency.

Table 20 Input voltage

60 Hz

50 Hz

(L-L)

(L-L)

 

 

208V

208V

 

 

380V

380V

 

 

400V

400V

 

 

415V

415V

 

 

480V

-

 

 

600V

-

 

 

14.1.3 Output Voltage

The output voltage shall be three phase AC (4 wire-plus-ground).

Table 21 Output voltage

60 Hz

50 Hz

(L-L/L-N)

(L-L/L-N)

 

 

208/120V

208/120V

 

 

380/220V

380/220V

 

 

400/230V

400/230V

 

 

415/240V

415/240V

 

 

14.1.4 System Current Ratings

These ratings are based upon continuous switch current rating. All units are 100% continuous cur- rent rated. Some ratings are not available in certain voltages.

Table 22 System current ratings

Current

250A

400A

600A

800A

14.1.5Grounding

Refer to 4.2 - System Grounding for specifications and instructions regarding grounding.