Event Message Help Text
135
CB2 (S2) OPEN
Circuit Breaker 2 (for Source 2) Open
Circuit Breaker 2 is not closed. CB1 is only assigned to Source 2.
Check that the Circuit Breaker 2 switch is in the desired position.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
CB4 (S1 BYP) CLOSED
Circuit Breaker 4 (Source 1 Bypass Breaker) Closed
Circuit breaker 4 is not open. The input from Source 1 is bypassing the Static Transfer Switch2 Power Distribu-
tion Unit.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
CB5 (S1 BYP) CLOSED
Circuit Breaker 5 (Source 2 Bypass Breaker) Closed
Circuit breaker 5 is not open. The input from Source 2 is bypassing the Static Transfer Switch2 Power Distribu-
tion Unit.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
CB3 (OUTPUT) OPEN
Circuit Breaker 3 (Output breaker) Open
Circuit breaker 3 is not closed. This circuit breaker is assigned to the output load. The power flow to the load
cannot flow through the Static Transfer Switch2 Power Distribution Unit.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.